Plan Review Notes
Plan Review Notes For Permit 07011041
Permit Number 07011041
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-01 17:25:18 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE SHOW COMPLIANCE WITH CHAPTER 13 OF THE
 FLORIDA BUILDING CODE. SPECIFICALLY 13-415, FOR THE
 PURPOSE OF THIS REVIEW. LOCATE ALL DEVICES NEEDED FOR
 COMPLIANCE ON THE PLAN. SUBMIT CALCULATIONS AND
 INDICATE METHOD ON APPROPRIATE FORM.
  
 2} SHEET E0-1, ELECTRICAL SPECIFICATIONS. THE CODE
 ARTICLES INCORRECTLY REFERENCES THE 2002 NEC. THE 2005
 WAS ADOPTED EFFECTIVE 12/8/06. PLEASE CHANGE THIS TO
 ELIMINATE ANY CONFUSION IN THE FIELD.
  
 3} SHEET E3.1, CIRCUIT L4C-8 IS AT THE COPIER.THE PANEL
 SCHEDULE LISTS THIS CIRCUIT AS A PRINTER.
  
 4} PLEASE CORRECT THE BUILDING ADDRESS ON THE PLANS TO
 READ 444 W. RAILROAD AVENUE, AS THERE ARE TWO BUILDINGS
 AT 3RD AND WEST RAILROAD AVENUE.LEAVE THE SUITE NUMBER
 FOR CLARITY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH