Plan Review Notes
Plan Review Notes For Permit 07011040
Permit Number 07011040
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-20 09:10:44 
  
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED
 FROM THE PREVIOUS REVIEW:
  
 "2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING".STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.NOTE #1 ADDRESSING THIS ISSUE
 STATES THAT THE "SPACES LESS THAN 5000 SF". PLEASE SEE
 13-101.1.4. A "SPACE" IS NOT A "BUILDING", THE
 "BUILDING" IS MORE THAN 5000 SF, THE "SPACE" MUST
 COMPLY. SHOW COMPLIANCE ON THE DRAWING, NOT IN THE
 NOTES.106.1.1 FBC.
  
 3} PLEASE INDICATE CONDUCTOR SIZE ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED. THE
 BRANCH CIRCUIT CONDUCTOR SIZES,AS WELL AS THE FEEDER,
 NEED TO BE ON THE SCHEDULE. 106.3.5.1.2(1), FBC AS
 AMENDED.
  
 THESE COMMENTS ARE FROM THIS REVIEW.
  
 4} SHEET #5 OF THE CALCULATIIONS INCORRECTLY INDICATES
 "PASSES", THERE ARE NO LIGHTING CONTROLS SHOWN ON THE
 DRAWING.
  
 5} SHEET #2 OF THE INPUT DATA REPORT INCORRECTLY
 INDICATES 1 FLUORESCENT FIXTURE@ 1300 WATTS FOR THE
 LIGHTING FOR THE SPACE. PLEASE CORRECT INDICATING ALL
 FIXTURES BEING USED.
  
 6} PROVIDE A FIXTURE SCHEDULE THAT MATCHES WHAT THE
 ENERGY CALCULATIONS INDICATES.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]