Plan Review Notes For Permit 07011040 |
Permit Number |
07011040 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-06 14:46:51 | ***DENIED*** | | | | 1) PLEASE INDICATE HOW THE REQUIREMENTS OF NFPA 101, | | SECTION 7.2.1.5 WILL BE COMPLIED WITH IF KEYED LOCKS | | ARE ALLOWED ON DOORS. | | | | 2) WHAT WOULD PREVENT THE DOOR TO EXISTING STORAGE 108 | | FROM OBSTRUCTING THE EXIT WHEN DOOR IS IN THE OPEN | | POSITION. | | | | 3) WILL FOODS THAT PRODUCE GREASE LADEN VAPORS BE | | COOKED AT ANY TIME? | | | | 4) AN ADDITIONAL FIRE EXTINGUISHER WILL BE REQUIRED | | NEAR THE FRONT EXIT. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | (561) 805-6722 OR 804-4756 |
|