Plan Review Notes
Plan Review Notes For Permit 07011040
Permit Number 07011040
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-06 14:46:51***DENIED***
  
 1) PLEASE INDICATE HOW THE REQUIREMENTS OF NFPA 101,
 SECTION 7.2.1.5 WILL BE COMPLIED WITH IF KEYED LOCKS
 ARE ALLOWED ON DOORS.
  
 2) WHAT WOULD PREVENT THE DOOR TO EXISTING STORAGE 108
 FROM OBSTRUCTING THE EXIT WHEN DOOR IS IN THE OPEN
 POSITION.
  
 3) WILL FOODS THAT PRODUCE GREASE LADEN VAPORS BE
 COOKED AT ANY TIME?
  
 4) AN ADDITIONAL FIRE EXTINGUISHER WILL BE REQUIRED
 NEAR THE FRONT EXIT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756