Plan Review Notes For Permit 07010997 |
Permit Number |
07010997 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-20 14:01:18 | ***DENIED*** | | | | 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT FA-01 | | AND FA-02 SEQUENCE OF OPERATION A. | | | | 2) FIRE ALARM TO COMPLY WITH THE REQUIREMENTS OF NFPA | | 72 IN REGARDS TO SURVIVABILITY. | | | | 3) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY | | ADDRESSABLE. | | | | 4) ONE SMOKE DETECTOR IS CALLED OUT IN THE PARKING | | GARAGE ON SHT FA-3. ? | | | | 5) MINI-HORN IN UNIT B7 (13) APPEARS TO BE MISSING. SHT | | FA-8 | | | | 6) STORAGE ROOM ON SHT FA-9 SHOWS NO SMOKE DETECTORS | | AND (2) STROBES ONLY. OTHER SHEETS ILLUSTRATE (1) | | SPEAKER/HORN AND (1) STROBE. | | | | 7) MINI-HORNS APPEAR TO HAVE BEEN LEFT OUT IN GREAT | | ROOMS ON SEVERAL SHEETS. | | | | 8) MINI-HORNS ARE MISSING IN UNITS B 11&12, AND MASTER | | BR C1. SHT FA-10 | | | | 9) PLANS INDICATE CENTRAL STATION. SHOULD READ FIRE | | ALARM TO BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW(561) 805-6722 | | FIRE PREVENTION(561) 804-4756 |
|