2007-04-04 16:51:29 | DENIED 2ND TIME |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| 1. **OK** |
| |
| 2. **NO** PLEASE PROVIDE ON THE SURVEY DIMENSIONS OF |
| THE GENERATOR IN RELATION TO STRUCTURES AND PROPERTY |
| LINES. |
| |
| 3. **NO** PLEASE PROVIDE INFORMATION OF GENERATOR |
| EXHAUST NOT BEING INSTALLED CLOSER THAN TEN FEET FROM |
| ANY OPENING INTO THE DWELLING STRUCTURE. THIS INCLUDES |
| DOORS, WINDOWS, AND ATTIC VENTILATION OPENINGS. PLEASE |
| PROVIDE THIS INFORMATION ON THE SURVEY. |
| |
| END OF COMMENTS: |
| |