Notes |
Date |
Text |
2007-03-28 06:54:50 | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PLEASE PROVIDE A CALCULATION FOR THE LOADS TO BE FED | | BY THE GENERATOR. THE CALCULATION GIVEN @ 126 AMPS IS | | OBVIOUSLY FOR THE ENTIRE RESIDENCE, AND MORE THAN THE | | GENERATOR OUTPUT OF 52.5 AMPS. 702.5, 2005 NEC. | | | | IT IS NOTED THAT THE INTENDED CIRCUUITS WERE LISTED, | | BUT A CALCULATION FOR THOSE IS NEEDED. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | FAX/:561/805-6676 |
|