 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE A CALCULATION FOR THE LOADS TO BE FED
 BY THE GENERATOR. THE CALCULATION GIVEN @ 126 AMPS IS
 OBVIOUSLY FOR THE ENTIRE RESIDENCE, AND MORE THAN THE
 GENERATOR OUTPUT OF 52.5 AMPS. 702.5, 2005 NEC.
  
 IT IS NOTED THAT THE INTENDED CIRCUUITS WERE LISTED,
 BUT A CALCULATION FOR THOSE IS NEEDED.
  