Plan Review Notes For Permit 07010969
Permit Number 07010969
Review Stop G
Sequence Number 1
Notes
Date Text
2007-02-13 10:08:29DENIED INCOMPLETE INFORMATION
 REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM
 BEACH RESIDENTIAL GENERATOR PERMIT APPLICATION
 REQUIREMENTS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE PROVIDE MANUFACTURER SPECIFICATIONS
 REGAURDING CLEARENCES FOR THE GENERATOR TO STRUCTURES.
  
 2. PLEASE PROVIDE ON THE SURVEY DIMENSIONS OF THE
 GENERATOR IN RELATION TO STRUCTURES AND PROPERTY
 LINES.
  
 3. PLEASE PROVIDE INFORMATION OF GENERATOR EXHAUST NOT
 BEING INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING
 INTO THE DWELLING STRUCTURE. THIS INCLUDES DOORS,
 WINDOWS, AND ATTIC VENTILATION OPENINGS.
  
 END OF COMMENTS:
  