Plan Review Notes For Permit 07010969 |
Permit Number |
07010969 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-02 14:02:54 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND | | RECOMMENDATION, REGARDING CLEARANCES FOR THE | | GENERATOR. | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | RESUBMITTING. | | | | 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | | | | | | | | | |
|