Plan Review Notes
Plan Review Notes For Permit 07010969
Permit Number 07010969
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-02 14:02:54 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FOR THE
 GENERATOR.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  