Plan Review Notes
Plan Review Notes For Permit 07010924
Permit Number 07010924
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-05 13:17:06*****DENIED*****
  
  
 1.PLEASE EXPLAIN ON SHEET C6 SEC BB FIRE ACCESS
 VARING 15' TO 20'.PER NFPA 1 2003 ED.FIRE DEPT.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WITDTH OF NOT
 LESS THAN 20 FT. AND AN UNOBSTRUCTED VERTICAL CLEARANCE
 OF NOT LESS THAN 13FT 6IN.
  
  
  
  
 CAPT MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 (561) 805-6722


Account Summary | Usage Policy | Privacy Policy