2007-01-30 14:27:11 | ***DENIED*** | | | | 1) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | REQUIREMENTS. | | | | 2) FIRE ALARMS THAT SUPERVISE FIRE SPRINKLER SYSTENS | | SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | PROOF OF CERTIFICATE WILL BE REQUIRED AT THE TIME OF | | FINAL INSPECTION OF FIRE ALARM. | | | | 3) PLEASE SUBMIT MANUFACTURER SPECIFICATION BOOKS FOR | | FIRE ALARM PANEL AND ALL ASSOCIATED EQUIPMENT AND | | DEVICES. | | | | 4) FLOW SWITCHES WHEN ACTIVATED SHALL INITIATE AN ALARM | | WITHIN 45-60 SECONDS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | (561) 805-6722 OR 804-4756 |
|