Plan Review Notes For Permit 07010897 |
Permit Number |
07010897 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-02-20 18:30:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | 1.) THE ANCHOR SPACING YOU HAVE SPECIFIED IS NOT | | COMPLIANT FOR THE LARGER OPENINGS.SEE SHEET 13 OF THE | | PRODUCT APPROVAL; YOU HAVE HIGHLIGHTED 10INCH, 7FEET. | | THE LARGEST OPENING IS OVRE 10FEET, SO YOU WOULD BE | | REQUIRED TO USE THE 11' CHART.CHECK ALL CONNECTIONS. | | |
|