Plan Review Notes For Permit 07010849 |
Permit Number |
07010849 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-03-01 15:27:37 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)HORIZONTAL SPANS DO NOT CORRELATE WITH OPENING | | SIZES. | | | | 2.)TWO COMPLETE SETS OF ALL DOCUMENTS REQUIRED.ONLY | | ONE INSTALLATION SCHEDULE WAS PROVIDED. | | | | 3.)HOW HAVE YOU ARRIVED AT THE DESIGN PRESSURE OF | | -31.6? | | |
|