Plan Review Notes
Plan Review Notes For Permit 07010804
Permit Number 07010804
Review Stop P
Sequence Number 2
Notes
Date Text
2007-03-07 14:07:07DENIED 2ND TIME
 REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING
 POOLS:
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1) ** NO**,FBC-2004 SEC. 424.2.6.6.5, OR FBCR-2004
 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR
 INDICATE THE MAKE AND MODEL NUMBER ON THE RESUBMITTED
 PRINTS. PLEASE REFERENCE THE ATTACHED EXAMPLE OF VACUUM
 OR PRESSURE CLEANER FITTING WITH THE ABOVE
 INFORMATION.
  
 2) **NO**,FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: PLEASE REFERENCE THE ATTACHED EXAMPLE OF AN
 1-1/2" ATMOSPHERIC VENT TABLE COMPLYING WITH 3 SECOND
 RELEASE. PLEASE SUBMIT A TABLE WITH 1" VENT COMPLYING
 WITH 3 SECOND RELEASE ON THE RESUBMITTAL.
  
 3) OK
  
 **IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW:
 WHEN RESUBMITTING, PLEASE REPLACE ONLY SHEETS WHICH
 HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  