2007-03-07 14:07:07 | DENIED 2ND TIME |
| REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING |
| POOLS: |
| |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| 1) ** NO**,FBC-2004 SEC. 424.2.6.6.5, OR FBCR-2004 |
| SEC. R4101.6.6.5 WHERE |
| PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| FITTING SHALL BE LOCATED AT LEAST 6" AND |
| NOT GREATER THAN 12" BELOW THE MINIMUM |
| OPERATING WATER LEVEL OR AS AN |
| ATTACHMENT TO THE SKIMMER. |
| NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR |
| INDICATE THE MAKE AND MODEL NUMBER ON THE RESUBMITTED |
| PRINTS. PLEASE REFERENCE THE ATTACHED EXAMPLE OF VACUUM |
| OR PRESSURE CLEANER FITTING WITH THE ABOVE |
| INFORMATION. |
| |
| 2) **NO**,FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. PLEASE |
| SUBMIT AN ENGINEERED TABLE FOR "VENT |
| PIPE MAXIMUM LENGTH" INDICATING PUMP |
| SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| OF THE 1" PVC VENT PIPE, FROM |
| WHERE IT STARTS TO WHERE IT ENDS UP, |
| COMPLYING WITH THE THREE SECOND RELEASE. |
| NOTE: PLEASE REFERENCE THE ATTACHED EXAMPLE OF AN |
| 1-1/2" ATMOSPHERIC VENT TABLE COMPLYING WITH 3 SECOND |
| RELEASE. PLEASE SUBMIT A TABLE WITH 1" VENT COMPLYING |
| WITH 3 SECOND RELEASE ON THE RESUBMITTAL. |
| |
| 3) OK |
| |
| **IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: |
| WHEN RESUBMITTING, PLEASE REPLACE ONLY SHEETS WHICH |
| HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |