2007-02-05 13:52:17 | DENIED |
| REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING |
| POOLS |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1) FBC-2004 SEC. 424.2.6.6.5, OR |
| FBCR-2004 SEC. R4101.6.6.5 WHERE |
| PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| FITTING SHALL BE LOCATED AT LEAST 6" AND |
| NOT GREATER THAN 12" BELOW THE MINIMUM |
| OPERATING WATER LEVEL OR AS AN |
| ATTACHMENT TO THE SKIMMER. |
| NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR |
| INDICATE MAKE AND MODEL NUMBER ON RESUBMITTED PRINTS. |
| |
| 2) FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. PLEASE |
| SUBMIT AN ENGINEERED TABLE FOR "VENT |
| PIPE MAXIMUM LENGTH" INDICATING PUMP |
| SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| OF THE 1" PVC VENT PIPE, FROM |
| WHERE IT STARTS TO WHERE IT ENDS UP, |
| COMPLYING WITH THE THREE SECOND RELEASE. |
| |
| 3) SHEET 5 OF 5 GENERAL NOTES NUMBER 18: PER FBC-2004 |
| SECTION 424.2.20 AND R4101.20, PLEASE INDICATE THE POOL |
| AND SPA TURN OVER TIME ON SHEET 3 OF 5 SPECIFICATIONS |
| ON THE RESUBMITTAL. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |