Plan Review Notes For Permit 07010787 |
Permit Number |
07010787 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-01 11:11:09 | *** DENIED *** | | 1) PLEASE SUBMIT INFORMATION REGARDING DIESEL FUEL TANK | | CAPACITY. | | | | 2) PLEASE STATE ON PLANS DISTANCE FROM FUEL TANK TO LOT | | LINE AND TO BUILDING. | | | | 3) 4) PLEASE BE ADVISED, INSTALLATION OF | | OUTSIDE ABOVEGROUND TANKS. | | 7.9.2 A TANK OR TANKS WHOSE CAPACITY | | DOES NOT EXCEED 660 GAL (2500 L) SHALL | | BE PERMITTED TO BE INSTALLED OUTSIDE OF | | AND ADJACENT TO A BUILDING, PROVIDED | | THEY ARE SEPARATED FROM THE NEAREST LINE | | OF ADJOINING PROPERTY BY THE FOLLOWING | | MINIMUM DISTANCE: | | (1)5 FT (1.5 M) FOR TANKS NOT | | EXCEEDING 275 GAL (1040 L) CAPACITY | | (2)10 FT (3 M) FOR TANKS GREATER | | THAN 275 GAL (1040 L) CAPACITY, BUT NOT | | EXCEEDING 660 GAL (2500 L) CAPACITY | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|