Plan Review Notes
Plan Review Notes For Permit 07010787
Permit Number 07010787
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-01 11:11:09*** DENIED ***
 1) PLEASE SUBMIT INFORMATION REGARDING DIESEL FUEL TANK
 CAPACITY.
  
 2) PLEASE STATE ON PLANS DISTANCE FROM FUEL TANK TO LOT
 LINE AND TO BUILDING.
  
 3) 4) PLEASE BE ADVISED, INSTALLATION OF
 OUTSIDE ABOVEGROUND TANKS.
 7.9.2 A TANK OR TANKS WHOSE CAPACITY
 DOES NOT EXCEED 660 GAL (2500 L) SHALL
 BE PERMITTED TO BE INSTALLED OUTSIDE OF
 AND ADJACENT TO A BUILDING, PROVIDED
 THEY ARE SEPARATED FROM THE NEAREST LINE
 OF ADJOINING PROPERTY BY THE FOLLOWING
 MINIMUM DISTANCE:
 (1)5 FT (1.5 M) FOR TANKS NOT
 EXCEEDING 275 GAL (1040 L) CAPACITY
 (2)10 FT (3 M) FOR TANKS GREATER
 THAN 275 GAL (1040 L) CAPACITY, BUT NOT
 EXCEEDING 660 GAL (2500 L) CAPACITY
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.