Plan Review Notes For Permit 07010787 |
Permit Number |
07010787 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-30 17:00:33 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | THE SERVICE AND GENERATOR GEAR ON SAME | | SO THAT COMPLIANCE WITH | | 230.72(GROUPING), 225.31-39 FOR THE | | DISCONNECTING MEANS REQUIREMENTS AND | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | INDICATING RECOMMENDED SETBACKSFOR THE GENERATOR. | | SHOW COMPLIANCE ON THE SITE PLAN AND SURVEY. THE | | GENERATOR APPEARS TOO CLOSE TO THE RESIDENCE. | | | | 3} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | (TRANSFER SWITCHES, PANELS ETC.) | | AND PAD PER 108.3 FBC AS AMENDED. | | INCREASE THE VALUE AT THE COUNTER WHEN | | RESUBMITTING, AND GET A RECEIPT FROM THE | | PERMIT CLERK. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|