2007-02-12 10:47:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A
 BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL
 BE USED.
  
 2.)THE VALUE IS TOO LOW.INCLUDE ALL MATERIALS AND
 LABOR.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED.
  