2007-01-23 13:45:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. MORE INFORMATION REQUIRED. SUBMIT ARCHITECTURAL
 PLANS FOR THE FLOOR PLAN. SHOW ALL WALLS THAT WILL BE
 OPENED TO INSTALL THE TUB AND THE WASH MACHINE. SHOW
 THE EXISTING FLOOR PLAN AND INDICATE THE SANITARY,
 VENT, AND WATER RISER LOCATION. SUBMIT A PROPOSED FLOOR
 PLAN SHOWING THE LOCATION OF THE NEW TUB, SHOWER AND
 THE LOCATION OF THE NEW WASH MACHINE. PLEASE INDICATE
 IF ANY COMMON AREA WALLS ARE INVOLVED. THE FIRE RATING
 OF ANY COMMON WALLS SHALL NOT BE COMPROMISED.SECTION
 106.1.2. IF PLANS ARE NOT SIGNED, SEALED, DATED BY A
 DESIGN PROFESSIONAL, THE PERSON THAT DESIGNS THE PLANS
 SHALL PRINT THEIR NAME AND SIGN THE PLANS. THE BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8" SCALE. SECTION
 106.1.3.
  
 2. IF IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF THE ALTERATION APPEARS TO
 UNDERESTIMATED ON THE APPLICATION THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, PLUMBING, INTERIOR FUNISH, ARCHITECTURAL
 AND DESIGN FEES, OVERHEAD AND PROFIT, EXCLUDING ONLY
 LAND VALUE.SUMBIT A SIGNED CONTRACT WITH THE
 APPLICATION. ALL OTHER WORK WILL BE VALUED PER
 MARSHALLS & SWIFT. THE VALUE OF $2,400 IS TOO LOW FOR
 THIS WORK. PLEASE READJUST THE VALUE TO REFLECT THE
 TRUE VALUE OF THE JOB.
  
 3. SUBMIT A SANITARY AND A WATER RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, VENTS FOR THE
 SANT. RISER, AND ALL PIPE SIZES, VALVES AND REQUIRED
 WATER HAMMER ARRESTORS FOR THE WATER RISER. SECTION
 106.3.5.1.3(3)(4)(6)(10)(13).
  