2007-02-16 14:48:59 | ----------------DENIED----------------------- |
| |
| 1. AHU H IN STORAGE ROOM,PG M8.1.3 SHOWS SUPPLY AND |
| RETURN PENETRATING A ONE HOUR RATED WALL INTO A MEANS |
| OF EGRESS CORRIDOR. PLEASE SHOW HOW THESE OPENINGS WILL |
| BE PROTECTED PER FBC,M 607 |
| |
| 2. RELATED TO COOMENT 1, EQUIPMENTS AND DUCTWORK FOR |
| EXIT ENCLOSURE VENTILLATION SHALL COMPLY WITH ONE OF |
| THE THREE OPTIONS AS LISTED IN FBC,M 401.4. |
| |
| 3. PLANS INDICATE A WATER HEATER LOCATED IN A/C CLOSET. |
| AHU MOUNTING DETAIL DOES NOT SHOW ALLOWANCE FOR A WATER |
| HEATER. LOCATION OF WATER HEATER UNDER THAT AHU WILL |
| CONFLICT WITH AUXILIARY DRAIN PAN USED FOR OVERFLOW |
| PROTECTION. PLEASE CLARIFY SHOWING COMPLIANCE WITH |
| FBC,M 307.2.3 |
| |
| 4. SUBMIT A HORIZONTAL BUILDING CONDENSATE DRAIN |
| ISOMETRIC DIAGRAM SHOWING ALL PIPE SIZES, MATERIAL AND |
| INDICATE WHERE THE CONDENSATE TERMINATES. SUBMIT |
| VERTICAL RISER DIAGRAMS SHOWING ALL PIPE SIZES, |
| MATERIAL, VENTS, ETC PER FBC 106.3.5.1.3(4)(13) |
| |
| 5. AHU DETAIL CALLS FOR PVC PIPE TO RUN TO AUXILIARY |
| DRAIN PAN. PVC CAN NOT BE LOCATED IN A PLENUM PER FBC,M |
| 602.2.1. |
| |
| 6. PRE-ENGINEERED A/C STANDS (FOR ROOFTOP) ARE |
| CONSIDERED STRUCTURAL COMPONENTS AS DEFINED UNDER FAC |
| 9B-72. THEREFORE, PRODUCT APPROVALS MUST BE SUBMITTED |
| AT TIME OF APPLICATION. |
| |
| 7. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING |
| COMPLIANCE WITH THE REQUIREMENTS OF FBC,M CHAPTER 403. |
| |
| 8. FIRE DAMPER DETAIL: FIRE DAMPERS, SMOKE DAMPERS, |
| COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS PER FBC,M 607.2 |
| |
| 9. SHAFTS TERMINATING AT 2ND FLOOR SLAB SHALL HAVE AN |
| ENCLOSURE AT THE BOTTOM OF THE SHAFT PER FBC 707.11. |
| |
| 10 PLEASE SUBMIT INFORMATION FROM THE A/C SPLIT SYSTEMS |
| MANUFACTURER SHOWING PIPE SIZES FOR LONG-LINE |
| APPLICATIONS AS WELL AS ALLOWABLE ELEVATION DIFFERENCES |
| BETWEEN SPLIT SYSTEM COMPONENTS. |
| |