2007-02-27 16:17:27 | *****DENIED***** |
| |
| |
| 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| NOT HINDER OR INTERFERE WITH ACCESS TO THE PROPERTY OR |
| THE VICINITY THEREOF (INCLUDING FIRE LANES). |
| |
| 04.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE |
| BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF |
| WORK.IF SO, THIS WILL BE PERMITTED ONLY WHERE |
| REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION |
| FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE |
| ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ |
| ARE IN PLACE. |
| |
| 05.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| 80. |
| |
| 06.PLEASE LIST THE FIRE RATING FOR THE DOORS LEADING |
| TO THE STAIR TOWERS (MARKED AS 2). |
| |
| 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM |
| BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6" IN |
| HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 08.PLEASE INDICATE THE INTERIOR FINISH |
| CLASSIFICATIONS FOR THE WALLS AND CEILINGS FOR THE |
| EXITS, EXIT ACCESS CORRIDORS, AND OTHER SPACES. |
| |
| 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING THE |
| TRAVEL DISTANCE TO THE EXITS.THE LOCATION OF THE |
| 2A:10BC RATED FIRE EXTINGUISHERS (SATISFYING THE 75 |
| FEET TRAVEL DISTANCE) AND SMOKE ALARMS MAY ALSO BE |
| INCLUDED. |
| |
| 10.IT IS NOTED THAT THIS BUILDING IS SPRINKLERED, |
| PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| SHOULD THERE BE A MODIFICATION TO THIS SYSTEM DUE TO |
| THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE |
| REQUIRED. |
| |
| 11.IT IS ASSUMED THAT THIS BUILDING HAS A FIRE ALARM |
| SYSTEM, PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM |
| SYSTEM.SHOULD THERE BE A MODIFICATION TO THIS SYSTEM |
| DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT |
| WILL BE REQUIRED. |
| |
| 12.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| FOR ALL THE GUARDRAILS AND HANDRAILS. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT |
| WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |