Date |
Text |
2007-01-30 16:51:49 | **** UNSAT **** |
| |
| *** IMPORTANT*** |
| * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND |
| PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE |
| RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE |
| WHICH WERE NOT MADE ON THIS REVIEW. |
| ** PLEASE ALSO KNOW THAT THIS IS A CHANGE IN OCCUPANCY |
| WHICH WILL REQUIRE TECHNICAL CODE COMPLIANCE FOR THE |
| CURRENT CODES AND WELL AS OTHER REQUIREMENTS FOR CODE |
| COMPLIANCE FOR BUILDING, FIRE ETC. |
| THERE ARE A SUBSTANTIAL AMOUNT OF ITEMS WHICH CAN NOT |
| BE REVIEWED AT THIS TIME. |
| |
| 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| CORRECT. |
| PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER |
| 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO |
| THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL, |
| PLUMBING BUILDING ETC. |
| PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM. |
| 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-20, 2003 |
| NFPA-101, 2003 NFPA-1. |
| |
| ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL |
| REVIEW ONLY. |
| |
| 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS |
| SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS, |
| STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC |
| 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE |
| THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH |
| PLANS. |
| PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE |
| INDICATED. |
| PLEASE SEE NO FIRE ALARM PLANS AND FIRE SPRINKLER PLANS |
| WERE SUBMITTED WHICH WILL BE REQUIRED FOR THE BASE |
| BUILDING PROTECTION AND IS REQUIRED TO BE SUBMITTED |
| WITH MAIN BUILDING PLANS FOR REVIEW OF THESE REQUIRED |
| ITEMS |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 3) NOTE: PLEASE SEE COMMENTS POSSIBLY FROM ZONING AND |
| BUILDING REVIEW WITH RESPECT TO PARKING AND REQUIRED |
| MINIMUM LIGHTING LEVELS AND LOCATIONS OF PARKING. |
| ZONING MAY COMMENT BASED ON DIVISION 4, DMP 86294. (NOT |
| AN ELECTRICAL REQUIREMENT, HOWEVER WILL AFFECT THE |
| ELECTRICAL PLANS. |
| |
| 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION |
| FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE |
| INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE |
| PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT |
| THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON |
| PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS |
| IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE |
| MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A |
| *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON |
| PLANS. |
| PLEASE BE SURE TO INCLUDE ANY LIGHTING CIRCUITING FROM |
| HOUSE PANELS ETC. |
| PLEASE KNOW THAT ANY PARKING ACROSS THE STREET WHICH IS |
| LOCATED ON ANOTHER LEGAL PROPERTY MAY NOT BE FED FROM |
| THIS BUILDING ELECTRICAL SERVICE. |
| ** PLEASE SEE FBC 2004. |
| FBC ADMIN SECTION 106.1.2 |
| |
| 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| |
| 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND |
| PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE. |
| PLEASE SEE ALL AREAS FOR COMMON AREAS WHICH ARE NOT |
| PART OF THE RESIDENTIAL SHALL BE SHOWN AND COMPLY WITH |
| THE 2006 REVISIONS TO THE 2004 FBC CHAPTER 13.PLEASE |
| SEE 13-415.1.AB.1 AND 13-415.2. |
| PLEASE SEE THAT ALL ELECTRICAL AS SHOWN ON PLANS SHALL |
| BE INCLUDED IN THE ENERGY CALCULATIONS AS WELL AS THE |
| ELECTRICAL IN ENERGY CALCULATIONS NEEDS TO BE SHOWN ON |
| PLANS.(PLEASE SEE ELEC ON CALCS NOT ON PLANS) |
| PLEASE SEE ALL RESIDENTIAL AREAS ARE STILL FIGURED INTO |
| ENERGY CALCULATIONS EVEN IF THOSE AREAS ARE EXEMPT FROM |
| AUTOMATED CONTROL DEVICES. |
| * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, |
| BY THE ENGINEER OF RECORD. 13-103.1.1.1 |
| |
| 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED |
| FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC |
| 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE ALL COMMON AREAS AND SEPARATE SPACES |
| CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. PLEASE |
| SEE THIS INCLUDES ALL FLOORS AND LEVELS. |
| |
| 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM |
| FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22, |
| 620.23, 620.24 AND 620.51. |
| PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM |
| AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT |
| FEED ANY OTHER AREAS. PLEASE SEE PLANSDO NOT INDICATE |
| THESE CIRCUITS AT THIS TIME AND AS COMPLETE CODE |
| COMPLIANCE FOR ELEVATOR ROOMS, CONTROLS, DETECTION |
| DEVICES ETC WILL BE REQUIRED TO THE MEET THE CURRENT |
| CODE IF NOT ALREADY. |
| PLEASE ALSO SEE THE STATE ELEVATOR CODE. |
| PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR |
| MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11, |
| 620.12 ETC. |
| |
| 9) NOTE:PLEASE SEE MISSING CIRCUITING ON SOME COMMON |
| AREAS ELECTRICAL FIXTURES AND DEVICES. PLEASE COMPLETE |
| ALL CIRCUITING ON PLANS AND CORRELATE WITH THE PANEL |
| SCHEDULE(S). |
| PLEASE SEE COMMENTS LATER WITH RESPECT TO MANY PANEL |
| SCHEDULES WHICH WERE NOT SUBMITTED FOR REVIEW. |
| 408.4, 310.16,ETC |
| PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| LIGHTS. |
| |
| 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON |
| PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND. |
| PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS |
| TIME. |
| FBC 106.1.2. |
| |
| 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, AND |
| ELECTRICAL EQUIPMENT ROOMS. PLEASE SEE OTHER ROOMS FOR |
| GENERATOR, FIRE PUMP ETC WILL ALSO REQUIRE THIS , |
| HOWEVER PLEASE SEE OTHER COMMENTS FOR RELOCATION OF |
| THESE WHICH WILL AFFECT THE LOCATIONS. |
| NFPA-101 7.8, 7.9 |
| NFPA-70 700.16, AND 700.12E. |
| |
| 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR |
| ALL EGRESS PATHS. |
| PLEASE SHOW COMPLETED ELECTRICAL PLANS FOR ALL EGRESS |
| STAIRS AND PATHS. PLEASE SHOW ALL EXISTING MEETING THE |
| CURRENT CODES OR NEW TO BE INSTALLED. PLEASE SEE |
| CIRCUITING AND TYPE OF FIXTURES ARE ALSO REQUIRED. |
| PLEASE SEE MINIMUM LEVELS UNDER NORMAL AND UNDER |
| EMERGENCY ARE REQUIRED FOR ALL EGRESS PATHS. THIS WOULD |
| INCLUDE ANY EGRESS FROM BASEMENT TO PUBLIC RIGHT OF WAY |
| AND EGRESS OUT OF BUILDING TO PUBLIC RIGHT OF WAY. |
| PLEASE SEE ANY STAIR AREAS OUTSIDE WHICH HAS NOT PLACED |
| THE OCCUPANT TO THE PUBLIC RIGHT OF WAY WILL REQUIRE |
| EMERGENCY ILLUMINATION AT THESE LOCATIONS. PLEASE SEE |
| NFPA-101 7.8.1.3, 7.9.2.2. |
| |
| 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE |
| AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| BE REVIEWED FOR CODE COMPLIANCE. PLEASE KNOW COMPLETE |
| CODE COMPLIANCE MUST BE MET. PLEASE SEE THERE ARE PANEL |
| SCHEDULES FOR NEW PANELS WHICH WERE NOT SUBMITTED OR |
| SHOWN. PLEASE SUBMIT ALL INFORMATION FOR EXISTING |
| SERVICE AND WHAT ALL THIS EXISTING EQUIPMENT IS |
| FEEDING. PLEASE BE SURE TO SEE COMMENTS WITH RESPECT TO |
| FIRE PUMP AND EPSS. |
| PLEASE SEE RISER SHOWS A NEW MDP ALSO, HOWEVER NOT |
| PANEL SCHEDULE WAS SUBMITTED OR SHOWN. PLEASE SEE OTHER |
| ELECTRICAL PANELS FOR FUTURE USE WERE NOT SUBMITTED. |
| PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| 110.26 ETC. |
| PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| |
| 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY |
| 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2. |
| PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED |
| FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM |
| CONTROL PANEL. |
| ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| NOT ACCEPTABLE TO THIS AHJ. |
| 110.3, 90.4. |
| |
| 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN |
| THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THAT |
| NO LOAD CALCULATIONS WERE SUBMITTED FOR NEW SERVICE OR |
| ANY EXISTING. PLEASE INDICATE LOAD SUMMARY FOR ALL OF |
| THE SERVICES AND HOW THESE SIZES WERE DERIVED. |
| PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR |
| CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| NOT BE DETERMINED AT THIS TIME. |
| PLEASE SEE ALL OF 220.(THERE ARE TOO MANY SECTIONS TO |
| LIST) |
| PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| LOADS AND LARGEST MOTORS LOADS AT 125%. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE |
| AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE |
| CORRELATE WITH THE DIVISION SPEC SUBMITTED. |
| 106.1.2. |
| NEC 110.9 |
| |
| 18) NOTE: PLEASE SEE 240.21C6 FOR MAIN DISCONNECTS OR |
| MAIN CIRCUIT BREAKERS REQUIRED ON THE SECONDARY SIDE OF |
| THE TRANSFORMERS CAN NOT BE VERIFIED AT THIS TIME. |
| PLEASE ALSO SEE 408.36 |
| |
| 19) NOTE: PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR |
| COMPLIANCE FOR THE EPSS/ EMERGENCY GENERATOR. PLEASE |
| SEE THERE ARE MANY ITEMS TO BE VERIFIED FOR BRING |
| EXISTING UP TO CODE. |
| A) PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT |
| CANDLES FOR ROOM. (ALSO PREVIOUS NOTE ABOVE FOR EM |
| BATTERY BACK UP LIGHTING REQUIRED. |
| B) PLEASE SEE THE LOCATION OF THE GENERATOR DOES NOT |
| APPEAR IT CAN BE LOCATED IN THE BASEMENT BASED ON THE |
| ELEVATION. PLEASE SEE 7.2.3* |
| PLEASE SEE SOME OFTHE FOLLOWING TEXT IS EXTRACTED |
| FROM THE CODE. |
| |
| A.7.2.3 EPSS EQUIPMENT SHOULD BE LOCATED ABOVE KNOWN |
| PREVIOUS FLOODING ELEVATIONS WHERE POSSIBLE. |
| A.7.2.4 WHEN INSTALLING THE EPSS EQUIPMENT AND RELATED |
| AUXILIARIES, ENVIRONMENTAL CONSIDERATIONS SHOULD BE |
| GIVEN, PARTICULARLY WITH REGARD TO THE INSTALLATION OF |
| THE FUEL TANKS AND EXHAUST LINES, OR THE EPS BUILDING, |
| OR BOTH. |
| TO PROTECT AGAINST DISRUPTION OF POWER IN THE FACILITY, |
| IT IS RECOMMENDED THAT THE TRANSFER SWITCH BE LOCATED |
| AS CLOSE TO THE LOAD AS POSSIBLE. THE FOLLOWING ARE |
| EXAMPLES OF EXTERNAL INFLUENCES: |
| (1)NATURAL CONDITIONS |
| (A)STORMS |
| (B)FLOODS |
| (C)EARTHQUAKES |
| (D)TORNADOES |
| (E)HURRICANES |
| (F)LIGHTNING |
| (G)ICE STORMS |
| (H)WIND |
| (I)FIRE |
| (2)HUMAN-CAUSED CONDITIONS |
| (A)VANDALISM |
| (B)SABOTAGE |
| (C)OTHER SIMILAR OCCURRENCES |
| (3)MATERIAL AND EQUIPMENT FAILURES |
| FOR NATURAL CONDITIONS, EPSS DESIGN SHOULD CONSIDER THE |
| "100-YEAR STORM" FLOODING LEVEL OR THE FLOODING LEVEL |
| PREDICTED BY THE SLOSH MODELS FOR A CLASS 4 HURRICANE. |
| SLOSH STANDS FOR SEA, LAKE, OVERLAND, SURGES BY |
| HURRICANES. |
| |
| THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS HOUSING |
| LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE DESIGNED AND |
| LOCATED TO MINIMIZE THE DAMAGE FROM FLOODING, INCLUDING |
| THAT CAUSED BY THE FOLLOWING: |
| (1)FLOODING RESULTING FROM FIRE FIGHTING |
| (2)SEWER WATER BACKUP |
| (3)SIMILAR DISASTERS OR OCCURRENCES |
| |
| C) PLEASE SEE THE MINIMUM CLEARANCE FOR ATS SWITCHES |
| CAN NOT BE VERIFIED AT THIS TIME. |
| D) PLEASE SEE 7.9.1 FOR FUEL SYSTEM REQUIREMENTS AS |
| WELL AS NFPA-20 2003 SECTION 9.6.2.2 THE FUEL SUPPLY |
| CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS OF FIRE |
| PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP |
| CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER |
| DEMANDS. |
| E) PLEASE SEE MANY ITEMS FOR THE EXISTING EMERGENCY |
| SYSTEM CAN NOT BE VERIFIED. THE INFORMATION WHICH NEEDS |
| TO BE SHOWN NEEDS TO BE PLACED ON PLANS AS IF THIS WAS |
| A NEW BUILDING BEING CONSTRUCTED UNDER THE CURRENT |
| CODES FOR THE ELECTRICAL AND EMERGENCY SYSTEMS. (EVEN |
| IF SHOWN AS EXISTING MEETING THE CURRENT CODE). |
| |
| 20) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE |
| OF WORK WILL NEED TO BE ADJUSTED ONCE ALL REVIEWS ARE |
| DONE AND PLANS ARE BROUGHT UP TO CODE. |
| PLEASE SEE FBC 108.3 ADMIN SECTION. |
| |
| 21) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S) |
| SHALL BE SPECIFIC TO ALL AREAS/ROOMS AND SPACES IN |
| WHICH THEY FEED. PLEASE SEE THE COMMENTARY SECTION OF |
| THE 2005 NEC WHICH EXPLAINS THIS.PLEASE SEE THE |
| REQUIREMENT THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| REQUIRED BY THIS SECTION. |
| PLEASE BE SURE TO CORRELATE PLANS AND CIRCUITING SHOWN |
| AT THIS TIME. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| |
| 22) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 |
| WHICH ARE REQUIRED FOR WALLS 2FT OR GREATER AND WITHIN |
| 6FT OF ANY DOOR OPENINGS. |
| |
| 23) NOTE: PLEASE SEE LOCATION OF BATHROOM GFI |
| RECEPTACLES WHICH ARE REQUIRED TO BE WITHIN 3FT OF THE |
| LAVATORIES EDGE; HOWEVER MAY NOT CROSS OVER ONE |
| LAVATORY TO UTILIZE THE RECEPT. |
| PLEASE SEE THIS CAN BE CORRECTED BY PLACING AN |
| ADDITIONAL GFI ON PLANS OR RELOCATING THE ONE ALREADY |
| SHOWN TO BE LOCATED IN BETWEEN THE TWO LAVS. |
| 210.52D |
| |
| 24) NOTE: PLEASE CLARIFY IF THIS BUILDING IS STILL |
| ADJOINED TO THE BUILDING ACROSS THE ALLEY ON THE SOUTH |
| SIDE. |
| PLEASE SEE THIS MAY AFFECT USE ETC. |
| |
| 25) NOTE: PLEASE INCLUDE ALL FIRE RATINGS FOR EXISTING |
| FPL VAULT WALLS. |
| PLEASE SEE BUILDING CODE REQUIREMENTS AS WELL AS NEC |
| 450. |
| |
| 26) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM SIZE OF OVER |
| CURRENT PROTECTION OF TRANSFORMER UNLESS MEETING NOTE |
| #3 IS 125%. |
| |
| 27) NOTE: PLEASE SEE GROUNDING ELECTRODE RISER AND |
| NOTES AS THIS STATES FOOTER STEEL TO BE PART OF THE |
| GROUNDING ELECTRODE SYSTEM. PLEASE KNOW AS THIS IS AN |
| EXISTING BUILDING AND NOT NEW, THE EXISTING FOOTER (IF |
| THEY CONTAINED STEEL) ARE NOT REQUIRED TO HAVE THE |
| ATTACHMENT MADE AS THE CUTTING/CHIPPING INTO AN |
| EXISTING FOOTER OF THIS AGE WOULD AFFECT THE STRUCTURAL |
| INTEGRITY OF THE FOOTER. PLEASE KNOW THAT THIS IS |
| PERMITTED HOWEVER NOT REQUIRED. IF SHOWN ON RISER THEN |
| THIS WILL BE REQUIRED. PLEASE KNOW THAT ANY STRUCTURAL |
| BUILDING STEEL WOULD BE REQUIRED. |
| PLEASE SEE 250.50 |
| |
| 28) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM |
| DOES NOT SEEM TO INCLUDE ANY CONNECTION TO THE FIRE |
| SPRINKLER PIPE(S) AS REQUIRED. 250.50, 250.104 EXISTING |
| OR NEW? |
| |
| 29) NOTE: PLEASE CLARIFY THE DUPLEX WHICH IS A |
| HALF/SWITCHED RECEPTACLE FOR THE DISPOSAL SHOWN ON |
| PLANS. PLEASE KNOW THAT IF THIS DEVICE IS NOT GOING TO |
| FEED BOTH THE DISHWASHER AND DISPOSAL AS TYPICALLY |
| DONE, THEN THIS WOULD BE REQUIRED TO BE A SINGLE |
| RECEPTACLE DEVICE NOT A DUPLEX. |
| PLEASE KNOW THAT IF INDEED THIS DUPLEX IS GOING TO FEED |
| BOTH THE DISPOSAL AND DISHWASHER THEN A 2-POLE CIRCUIT |
| BREAKER IS REQUIRED AND CORRECTION OF PANEL SCHEDULE |
| WILL NEED TO BE MADE. |
| PLEASE SEE 210.3, 210.4, 210.7, 210.21, 210.23 ETC. |
| |
| 30) NOTE: PLEASE SEE LOAD CALCULATIONS FOR UNITS ARE TO |
| BE DONE PER NEC 220.82/220.84. PLEASE SEE THAT AS THIS |
| IS NOT AN EXISTING UNIT, HOW IS THE FIRST 8KVA BEING |
| INDICATED AT 100%? PLEASE SEE THIS WOULD BE THE FIRST |
| 10KAV FOR NEW CONSTRUCTION. |
| |
| 31) NOTE: PLEASE CLARIFY ALL TRANSFORMERS BEING SHOWN |
| ON SITE PLANS. ARE THESE ALL FEEDING THIS BUILDING? |
| |
| 32) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INCLUDE |
| ANY METERING DEVICES FOR THE ELECTRICAL FEEDING |
| COMMERCIAL SPACES EITHER BY WAY OF CT OR METER CAN? |
| PLEASE SEE FPL SERVICE GUIDELINES AS THIS IS REQUIRED |
| TO BE INDICATED ON ELECTRICAL PLANS AT THIS TIME. |
| PLEASE |
| |
| 33) NOTE: PLEASE PROVIDE COMPLETE INFORMATION FOR FIRE |
| PUMP, FIRE PUMP CONTROLLER AND ALL ASSOCIATE |
| EQUIPMENT. |
| PLEASE SEE THE FIRE PUMP RISER AS SHOWN AND HOW |
| EQUIPMENT IS BEING FED FROM THE HOUSE SERVICE IS NOT |
| PERMITTED. PLEASE SEE RISER ALSO SHOWS THIS BEING FED |
| FROM OTHER SEPARATE SERVICE ALSO. |
| PLEASE SEE 2005NEC 695 AND 2003 NFPA-20 (ALL). |
| PLEASE INDICATE IF THESE ARE NEW TO BE INSTALLED OR |
| EXISTING WHICH MEETS CURRENT CODES. |
| PLEASE SEE THE LOCATIONS OF THE FIRE PUMP ETC NEEDS TO |
| BE LOCATED PER CODES GIVEN AS NOTED. |
| ** AS SHOWN CODE COMPLIANCE IS NOT ACHIEVED. |
| |
| 34) NOTE: PLEASE SEE 240.24, 110.26 AND 408.17 FOR |
| LOCATIONS OF OVER CURRENT PROTECTION IN STORAGE AREAS. |
| |
| PLEASE SEE AIR HANDLER UNITS WHICH IS BEING SHOWN IN |
| STORAGE CLOSETS WHICH IS NOT PERMITTED. |
| |
| 35) NOTE: PLEASE SEE ONE SET CONTAINING REPEATED |
| SHEETS. |
| PLEASE SUBMIT TWO COMPLETE SETS OF PLANS. PLEASE KNOW |
| BASED ON SCOPE OF WORK, VALUE, CONSTRUCTION, AND THE |
| SIZE OF THE EXISTING BUILDING ALONG WITH OTHER |
| CONSIDERATIONS, THIS MAY REQUIRE AN ON-SITE INSPECTOR? |
| IF THIS IS THE CASE, THEN THREE SETS OF SIGNED, DATED |
| AND SEALED PLANS WILL BE REQUIRED. |
| 109.3.6, 106.1.2, 106.3.5.1.2 |
| |
| 36) NOTE: PLEASE SEE 109.3.6.4.4 |
| PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN |
| ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: * |
| TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA |
| STATUTES) 633. |
| THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE |
| AND/OR TITLE BLOCKS. |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-01-30 08:35:29 | IN ELEC FOR REVIEW |