Plan Review Notes
Plan Review Notes For Permit 07010773
Permit Number 07010773
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-30 16:51:49**** UNSAT ****
  
 *** IMPORTANT***
 * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND
 PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE
 RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE
 WHICH WERE NOT MADE ON THIS REVIEW.
 ** PLEASE ALSO KNOW THAT THIS IS A CHANGE IN OCCUPANCY
 WHICH WILL REQUIRE TECHNICAL CODE COMPLIANCE FOR THE
 CURRENT CODES AND WELL AS OTHER REQUIREMENTS FOR CODE
 COMPLIANCE FOR BUILDING, FIRE ETC.
 THERE ARE A SUBSTANTIAL AMOUNT OF ITEMS WHICH CAN NOT
 BE REVIEWED AT THIS TIME.
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER
 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO
 THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL,
 PLUMBING BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-20, 2003
 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL
 REVIEW ONLY.
  
 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS
 SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS,
 STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC
 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE
 THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH
 PLANS.
 PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE
 INDICATED.
 PLEASE SEE NO FIRE ALARM PLANS AND FIRE SPRINKLER PLANS
 WERE SUBMITTED WHICH WILL BE REQUIRED FOR THE BASE
 BUILDING PROTECTION AND IS REQUIRED TO BE SUBMITTED
 WITH MAIN BUILDING PLANS FOR REVIEW OF THESE REQUIRED
 ITEMS
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE COMMENTS POSSIBLY FROM ZONING AND
 BUILDING REVIEW WITH RESPECT TO PARKING AND REQUIRED
 MINIMUM LIGHTING LEVELS AND LOCATIONS OF PARKING.
 ZONING MAY COMMENT BASED ON DIVISION 4, DMP 86294. (NOT
 AN ELECTRICAL REQUIREMENT, HOWEVER WILL AFFECT THE
 ELECTRICAL PLANS.
  
 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE
 INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE
 PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT
 THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON
 PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS
 IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE
 MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A
 *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON
 PLANS.
 PLEASE BE SURE TO INCLUDE ANY LIGHTING CIRCUITING FROM
 HOUSE PANELS ETC.
 PLEASE KNOW THAT ANY PARKING ACROSS THE STREET WHICH IS
 LOCATED ON ANOTHER LEGAL PROPERTY MAY NOT BE FED FROM
 THIS BUILDING ELECTRICAL SERVICE.
 ** PLEASE SEE FBC 2004.
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE.
 PLEASE SEE ALL AREAS FOR COMMON AREAS WHICH ARE NOT
 PART OF THE RESIDENTIAL SHALL BE SHOWN AND COMPLY WITH
 THE 2006 REVISIONS TO THE 2004 FBC CHAPTER 13.PLEASE
 SEE 13-415.1.AB.1 AND 13-415.2.
 PLEASE SEE THAT ALL ELECTRICAL AS SHOWN ON PLANS SHALL
 BE INCLUDED IN THE ENERGY CALCULATIONS AS WELL AS THE
 ELECTRICAL IN ENERGY CALCULATIONS NEEDS TO BE SHOWN ON
 PLANS.(PLEASE SEE ELEC ON CALCS NOT ON PLANS)
 PLEASE SEE ALL RESIDENTIAL AREAS ARE STILL FIGURED INTO
 ENERGY CALCULATIONS EVEN IF THOSE AREAS ARE EXEMPT FROM
 AUTOMATED CONTROL DEVICES.
 * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED,
 BY THE ENGINEER OF RECORD. 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED
 FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE ALL COMMON AREAS AND SEPARATE SPACES
 CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. PLEASE
 SEE THIS INCLUDES ALL FLOORS AND LEVELS.
  
 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM
 FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22,
 620.23, 620.24 AND 620.51.
 PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM
 AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT
 FEED ANY OTHER AREAS. PLEASE SEE PLANSDO NOT INDICATE
 THESE CIRCUITS AT THIS TIME AND AS COMPLETE CODE
 COMPLIANCE FOR ELEVATOR ROOMS, CONTROLS, DETECTION
 DEVICES ETC WILL BE REQUIRED TO THE MEET THE CURRENT
 CODE IF NOT ALREADY.
 PLEASE ALSO SEE THE STATE ELEVATOR CODE.
 PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR
 MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11,
 620.12 ETC.
  
 9) NOTE:PLEASE SEE MISSING CIRCUITING ON SOME COMMON
 AREAS ELECTRICAL FIXTURES AND DEVICES. PLEASE COMPLETE
 ALL CIRCUITING ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE(S).
 PLEASE SEE COMMENTS LATER WITH RESPECT TO MANY PANEL
 SCHEDULES WHICH WERE NOT SUBMITTED FOR REVIEW.
 408.4, 310.16,ETC
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
  
 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND.
 PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS
 TIME.
 FBC 106.1.2.
  
 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP
 LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, AND
 ELECTRICAL EQUIPMENT ROOMS. PLEASE SEE OTHER ROOMS FOR
 GENERATOR, FIRE PUMP ETC WILL ALSO REQUIRE THIS ,
 HOWEVER PLEASE SEE OTHER COMMENTS FOR RELOCATION OF
 THESE WHICH WILL AFFECT THE LOCATIONS.
 NFPA-101 7.8, 7.9
 NFPA-70 700.16, AND 700.12E.
  
 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR
 ALL EGRESS PATHS.
 PLEASE SHOW COMPLETED ELECTRICAL PLANS FOR ALL EGRESS
 STAIRS AND PATHS. PLEASE SHOW ALL EXISTING MEETING THE
 CURRENT CODES OR NEW TO BE INSTALLED. PLEASE SEE
 CIRCUITING AND TYPE OF FIXTURES ARE ALSO REQUIRED.
 PLEASE SEE MINIMUM LEVELS UNDER NORMAL AND UNDER
 EMERGENCY ARE REQUIRED FOR ALL EGRESS PATHS. THIS WOULD
 INCLUDE ANY EGRESS FROM BASEMENT TO PUBLIC RIGHT OF WAY
 AND EGRESS OUT OF BUILDING TO PUBLIC RIGHT OF WAY.
 PLEASE SEE ANY STAIR AREAS OUTSIDE WHICH HAS NOT PLACED
 THE OCCUPANT TO THE PUBLIC RIGHT OF WAY WILL REQUIRE
 EMERGENCY ILLUMINATION AT THESE LOCATIONS. PLEASE SEE
 NFPA-101 7.8.1.3, 7.9.2.2.
  
 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE. PLEASE KNOW COMPLETE
 CODE COMPLIANCE MUST BE MET. PLEASE SEE THERE ARE PANEL
 SCHEDULES FOR NEW PANELS WHICH WERE NOT SUBMITTED OR
 SHOWN. PLEASE SUBMIT ALL INFORMATION FOR EXISTING
 SERVICE AND WHAT ALL THIS EXISTING EQUIPMENT IS
 FEEDING. PLEASE BE SURE TO SEE COMMENTS WITH RESPECT TO
 FIRE PUMP AND EPSS.
 PLEASE SEE RISER SHOWS A NEW MDP ALSO, HOWEVER NOT
 PANEL SCHEDULE WAS SUBMITTED OR SHOWN. PLEASE SEE OTHER
 ELECTRICAL PANELS FOR FUTURE USE WERE NOT SUBMITTED.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY
 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2.
 PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED
 FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM
 CONTROL PANEL.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN
 THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THAT
 NO LOAD CALCULATIONS WERE SUBMITTED FOR NEW SERVICE OR
 ANY EXISTING. PLEASE INDICATE LOAD SUMMARY FOR ALL OF
 THE SERVICES AND HOW THESE SIZES WERE DERIVED.
 PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.(THERE ARE TOO MANY SECTIONS TO
 LIST)
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE
 AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED.
 106.1.2.
 NEC 110.9
  
 18) NOTE: PLEASE SEE 240.21C6 FOR MAIN DISCONNECTS OR
 MAIN CIRCUIT BREAKERS REQUIRED ON THE SECONDARY SIDE OF
 THE TRANSFORMERS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE ALSO SEE 408.36
  
 19) NOTE: PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR
 COMPLIANCE FOR THE EPSS/ EMERGENCY GENERATOR. PLEASE
 SEE THERE ARE MANY ITEMS TO BE VERIFIED FOR BRING
 EXISTING UP TO CODE.
 A) PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT
 CANDLES FOR ROOM. (ALSO PREVIOUS NOTE ABOVE FOR EM
 BATTERY BACK UP LIGHTING REQUIRED.
 B) PLEASE SEE THE LOCATION OF THE GENERATOR DOES NOT
 APPEAR IT CAN BE LOCATED IN THE BASEMENT BASED ON THE
 ELEVATION. PLEASE SEE 7.2.3*
 PLEASE SEE SOME OFTHE FOLLOWING TEXT IS EXTRACTED
 FROM THE CODE.
  
 A.7.2.3 EPSS EQUIPMENT SHOULD BE LOCATED ABOVE KNOWN
 PREVIOUS FLOODING ELEVATIONS WHERE POSSIBLE.
 A.7.2.4 WHEN INSTALLING THE EPSS EQUIPMENT AND RELATED
 AUXILIARIES, ENVIRONMENTAL CONSIDERATIONS SHOULD BE
 GIVEN, PARTICULARLY WITH REGARD TO THE INSTALLATION OF
 THE FUEL TANKS AND EXHAUST LINES, OR THE EPS BUILDING,
 OR BOTH.
 TO PROTECT AGAINST DISRUPTION OF POWER IN THE FACILITY,
 IT IS RECOMMENDED THAT THE TRANSFER SWITCH BE LOCATED
 AS CLOSE TO THE LOAD AS POSSIBLE. THE FOLLOWING ARE
 EXAMPLES OF EXTERNAL INFLUENCES:
 (1)NATURAL CONDITIONS
 (A)STORMS
 (B)FLOODS
 (C)EARTHQUAKES
 (D)TORNADOES
 (E)HURRICANES
 (F)LIGHTNING
 (G)ICE STORMS
 (H)WIND
 (I)FIRE
 (2)HUMAN-CAUSED CONDITIONS
 (A)VANDALISM
 (B)SABOTAGE
 (C)OTHER SIMILAR OCCURRENCES
 (3)MATERIAL AND EQUIPMENT FAILURES
 FOR NATURAL CONDITIONS, EPSS DESIGN SHOULD CONSIDER THE
 "100-YEAR STORM" FLOODING LEVEL OR THE FLOODING LEVEL
 PREDICTED BY THE SLOSH MODELS FOR A CLASS 4 HURRICANE.
 SLOSH STANDS FOR SEA, LAKE, OVERLAND, SURGES BY
 HURRICANES.
  
 THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS HOUSING
 LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE DESIGNED AND
 LOCATED TO MINIMIZE THE DAMAGE FROM FLOODING, INCLUDING
 THAT CAUSED BY THE FOLLOWING:
 (1)FLOODING RESULTING FROM FIRE FIGHTING
 (2)SEWER WATER BACKUP
 (3)SIMILAR DISASTERS OR OCCURRENCES
  
 C) PLEASE SEE THE MINIMUM CLEARANCE FOR ATS SWITCHES
 CAN NOT BE VERIFIED AT THIS TIME.
 D) PLEASE SEE 7.9.1 FOR FUEL SYSTEM REQUIREMENTS AS
 WELL AS NFPA-20 2003 SECTION 9.6.2.2 THE FUEL SUPPLY
 CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS OF FIRE
 PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP
 CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER
 DEMANDS.
 E) PLEASE SEE MANY ITEMS FOR THE EXISTING EMERGENCY
 SYSTEM CAN NOT BE VERIFIED. THE INFORMATION WHICH NEEDS
 TO BE SHOWN NEEDS TO BE PLACED ON PLANS AS IF THIS WAS
 A NEW BUILDING BEING CONSTRUCTED UNDER THE CURRENT
 CODES FOR THE ELECTRICAL AND EMERGENCY SYSTEMS. (EVEN
 IF SHOWN AS EXISTING MEETING THE CURRENT CODE).
  
 20) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE
 OF WORK WILL NEED TO BE ADJUSTED ONCE ALL REVIEWS ARE
 DONE AND PLANS ARE BROUGHT UP TO CODE.
 PLEASE SEE FBC 108.3 ADMIN SECTION.
  
 21) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S)
 SHALL BE SPECIFIC TO ALL AREAS/ROOMS AND SPACES IN
 WHICH THEY FEED. PLEASE SEE THE COMMENTARY SECTION OF
 THE 2005 NEC WHICH EXPLAINS THIS.PLEASE SEE THE
 REQUIREMENT THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
 PLEASE BE SURE TO CORRELATE PLANS AND CIRCUITING SHOWN
 AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 22) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52
 WHICH ARE REQUIRED FOR WALLS 2FT OR GREATER AND WITHIN
 6FT OF ANY DOOR OPENINGS.
  
 23) NOTE: PLEASE SEE LOCATION OF BATHROOM GFI
 RECEPTACLES WHICH ARE REQUIRED TO BE WITHIN 3FT OF THE
 LAVATORIES EDGE; HOWEVER MAY NOT CROSS OVER ONE
 LAVATORY TO UTILIZE THE RECEPT.
 PLEASE SEE THIS CAN BE CORRECTED BY PLACING AN
 ADDITIONAL GFI ON PLANS OR RELOCATING THE ONE ALREADY
 SHOWN TO BE LOCATED IN BETWEEN THE TWO LAVS.
 210.52D
  
 24) NOTE: PLEASE CLARIFY IF THIS BUILDING IS STILL
 ADJOINED TO THE BUILDING ACROSS THE ALLEY ON THE SOUTH
 SIDE.
 PLEASE SEE THIS MAY AFFECT USE ETC.
  
 25) NOTE: PLEASE INCLUDE ALL FIRE RATINGS FOR EXISTING
 FPL VAULT WALLS.
 PLEASE SEE BUILDING CODE REQUIREMENTS AS WELL AS NEC
 450.
  
 26) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM SIZE OF OVER
 CURRENT PROTECTION OF TRANSFORMER UNLESS MEETING NOTE
 #3 IS 125%.
  
 27) NOTE: PLEASE SEE GROUNDING ELECTRODE RISER AND
 NOTES AS THIS STATES FOOTER STEEL TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM. PLEASE KNOW AS THIS IS AN
 EXISTING BUILDING AND NOT NEW, THE EXISTING FOOTER (IF
 THEY CONTAINED STEEL) ARE NOT REQUIRED TO HAVE THE
 ATTACHMENT MADE AS THE CUTTING/CHIPPING INTO AN
 EXISTING FOOTER OF THIS AGE WOULD AFFECT THE STRUCTURAL
 INTEGRITY OF THE FOOTER. PLEASE KNOW THAT THIS IS
 PERMITTED HOWEVER NOT REQUIRED. IF SHOWN ON RISER THEN
 THIS WILL BE REQUIRED. PLEASE KNOW THAT ANY STRUCTURAL
 BUILDING STEEL WOULD BE REQUIRED.
 PLEASE SEE 250.50
  
 28) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM
 DOES NOT SEEM TO INCLUDE ANY CONNECTION TO THE FIRE
 SPRINKLER PIPE(S) AS REQUIRED. 250.50, 250.104 EXISTING
 OR NEW?
  
 29) NOTE: PLEASE CLARIFY THE DUPLEX WHICH IS A
 HALF/SWITCHED RECEPTACLE FOR THE DISPOSAL SHOWN ON
 PLANS. PLEASE KNOW THAT IF THIS DEVICE IS NOT GOING TO
 FEED BOTH THE DISHWASHER AND DISPOSAL AS TYPICALLY
 DONE, THEN THIS WOULD BE REQUIRED TO BE A SINGLE
 RECEPTACLE DEVICE NOT A DUPLEX.
 PLEASE KNOW THAT IF INDEED THIS DUPLEX IS GOING TO FEED
 BOTH THE DISPOSAL AND DISHWASHER THEN A 2-POLE CIRCUIT
 BREAKER IS REQUIRED AND CORRECTION OF PANEL SCHEDULE
 WILL NEED TO BE MADE.
 PLEASE SEE 210.3, 210.4, 210.7, 210.21, 210.23 ETC.
  
 30) NOTE: PLEASE SEE LOAD CALCULATIONS FOR UNITS ARE TO
 BE DONE PER NEC 220.82/220.84. PLEASE SEE THAT AS THIS
 IS NOT AN EXISTING UNIT, HOW IS THE FIRST 8KVA BEING
 INDICATED AT 100%? PLEASE SEE THIS WOULD BE THE FIRST
 10KAV FOR NEW CONSTRUCTION.
  
 31) NOTE: PLEASE CLARIFY ALL TRANSFORMERS BEING SHOWN
 ON SITE PLANS. ARE THESE ALL FEEDING THIS BUILDING?
  
 32) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INCLUDE
 ANY METERING DEVICES FOR THE ELECTRICAL FEEDING
 COMMERCIAL SPACES EITHER BY WAY OF CT OR METER CAN?
 PLEASE SEE FPL SERVICE GUIDELINES AS THIS IS REQUIRED
 TO BE INDICATED ON ELECTRICAL PLANS AT THIS TIME.
 PLEASE
  
 33) NOTE: PLEASE PROVIDE COMPLETE INFORMATION FOR FIRE
 PUMP, FIRE PUMP CONTROLLER AND ALL ASSOCIATE
 EQUIPMENT.
 PLEASE SEE THE FIRE PUMP RISER AS SHOWN AND HOW
 EQUIPMENT IS BEING FED FROM THE HOUSE SERVICE IS NOT
 PERMITTED. PLEASE SEE RISER ALSO SHOWS THIS BEING FED
 FROM OTHER SEPARATE SERVICE ALSO.
 PLEASE SEE 2005NEC 695 AND 2003 NFPA-20 (ALL).
 PLEASE INDICATE IF THESE ARE NEW TO BE INSTALLED OR
 EXISTING WHICH MEETS CURRENT CODES.
 PLEASE SEE THE LOCATIONS OF THE FIRE PUMP ETC NEEDS TO
 BE LOCATED PER CODES GIVEN AS NOTED.
 ** AS SHOWN CODE COMPLIANCE IS NOT ACHIEVED.
  
 34) NOTE: PLEASE SEE 240.24, 110.26 AND 408.17 FOR
 LOCATIONS OF OVER CURRENT PROTECTION IN STORAGE AREAS.
  
 PLEASE SEE AIR HANDLER UNITS WHICH IS BEING SHOWN IN
 STORAGE CLOSETS WHICH IS NOT PERMITTED.
  
 35) NOTE: PLEASE SEE ONE SET CONTAINING REPEATED
 SHEETS.
 PLEASE SUBMIT TWO COMPLETE SETS OF PLANS. PLEASE KNOW
 BASED ON SCOPE OF WORK, VALUE, CONSTRUCTION, AND THE
 SIZE OF THE EXISTING BUILDING ALONG WITH OTHER
 CONSIDERATIONS, THIS MAY REQUIRE AN ON-SITE INSPECTOR?
 IF THIS IS THE CASE, THEN THREE SETS OF SIGNED, DATED
 AND SEALED PLANS WILL BE REQUIRED.
 109.3.6, 106.1.2, 106.3.5.1.2
  
 36) NOTE: PLEASE SEE 109.3.6.4.4
 PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: *
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA
 STATUTES) 633.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE
 AND/OR TITLE BLOCKS.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-30 08:35:29IN ELEC FOR REVIEW