2007-02-16 17:52:44BUILDING REVIEW 4TH CHECKLIST:
  
 1- ENGINEER CALCULATIONS:
 A) ENGINEER REVISED LETTER STATES THAT"NAIL
 SPACING OF 9"O.C. INACCORDANCE WITH THE NOA WORKS
 EXCEPT IN THE CORNER WHERE THE SPACING NEEDS TO BE
 REDUCED TO 5"O.C.".CALCULATED DESIGN PRESSUREAT
 PERIMETER AREAIS-59.2PSF.ACCORDING TO PAGE 17 OF
 NOA 02-0212.07 SUBMITTED THE MAXIMUM DESIGN PRESSURE
 USING 11GA RING SHANK NAILS IS -52.5. THEREFORE,ALSO
 NEEDSNAIL ENHANCING AS ALLOWED BY GENERAL LIMITATION
 #7.REVISE AS REQUIRED.
  
 B) ENGINEER TO REVISEBASE SHEET FASTENER SPACING
 CALCULATIONS ON LAST PAGE OF CALCULATIONS SUBMITTED.
 ACCORDING TO RAS 117 CALCULATIONS SEC. 8.1 THE MAXIMUM
 DESIGN PRESSURES FOR THE ACCEPTED ASSEMBLY ARE THE ONES
 APPLICABLE TO THE ROOF AREA (1).REVISE FASTENER
 SPACING FOR ZONE 1 AS REQUIRED.
  
 C) ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 REGARDING DESIGN PROFESSIONAL DOCUMENTS AND PLAN REVIEW
 FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712