2007-02-12 18:06:42BUILDING REVIEW THIRD CHECKLIST:
 1- ENGINEERING CALCULATIONS SUBMITTED:
 A) FASTENER SPACING CALCULATIONS ARE WRONG. ENGINEER
 USED ANCHOR SPACING RN AND RS IN THE EQUATION ON LAST
 PAGE OF CALCULATIONS SUBMITTED.RAS 117 GENERAL
 EQUATION10.4.5 CALLS FOR ROW SPACING, NOT ANCHOR
 SPACING.NEED TO REVISE CALCULATIONS AS REQUIRED.
  
 B) ENGINEER USED 20SF AS THE TRIBUTARY AREA FOR THE
 DESIGN PRESSURES CALCULATIONS. NEED TO USE AT LEAT THE
 10SF TRIBUTARY AREA . THE EFFECTIVE WIND AREA SHALL NOT
 BE GREATERTHAN THE AREA THAT IS TRIBUTARY TO AN
 INDIVIDUAL FASTENER. SEE EFFECTIVE WIND AREA DEFINITION
 IN CHAPTER 16 FBC 2004.
  
 C) ENGINEER TO REVISE ALL FBC TABLES REFERENCED IN
 THE CALCULATIONS. NEED TO SEE REVISED FBC PAGES (BLUE
 PAGES) AND REVISE TABLES AS REQUIRED.
  
 D) ONLY THE DESIGN PRESSURES FOR ROOF ARE REQUIRED.
 THE REST OF THE DESIGN PRESSURES ARE NOT REQUIRED FOR A
 ROOF PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER