2007-01-30 18:58:10 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- ENGINEERING CALCULATIONS: |
| A) ENGINEER TO READ GENERAL LIMITATION #7 ON PAGE 20 |
| OF 20 OF NOA 02-0212.07 AND PROVIDE THE REQUIRED RAS |
| 117 CALCULATIONS. INFORMATION SUBMITTED ARE NOT THE RAS |
| 117 CALCULATIONS. |
| |
| B) CALCULATED DESIGN PRESSURES ARE TOO LOW COMPARE |
| TO TABLE 1609.6.2.1(2) OF 2004 FBC.ENGINEER TO |
| PROVIDE ACTUAL CALCULATIONS SHOWING CALCULATED DESIGN |
| PRESSURES. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| ***NOTE: ENGINEER TO CHECK ROOF PLAN.THIS HOUSE HAS |
| PITCH ROOF AND FLAT ROOF SYSTEMS, THEREFORE DESIGN |
| PRESSURES ARE DIFFERENT FOR EACH ROOF TYPE.ALSO, |
| CORRECT FLAT ROOF AREA NEED TO BE CONSIDER FOR DESIGN |
| PRESSURES CALCULATIONS. |
| |
| C) ENGINEER TO IDENTIFY SPECIFIC APPROVED FLAT ROOF |
| ASSEMBLY AND SPECIFIC FASTENING OPTIONS FOR WHICH HE IS |
| PROVIDING ENHANCED FASTENING CALCULATIONS.SEE NOA |
| SUBMITTED. COORDINATE WITH CONTRACTOR FOR SPECIFIC NAIL |
| TYPE TO BE USED. |
| |
| D) ENGINEER TO PROVIDE ENGINEERING FIRM'S |
| CERTIFICATE OF AUTHORIZATION AS REQUIRED BY FLORIDA |
| ADMINISTRATIVE CODE SEC. 61G15--23.001. |
| |
| E) CITY OF WEST PALM BEACH ADDRESS IS INCORRECT. |
| REVISE AS REQUIRED. |
| |
| 2-CORRECT NOA FOR ROOF TILE WAS REQUESTED ON PREVIOUS |
| CHECKLIST.SUCH NOA WAS NOT PROVIDED.THE ONLY |
| INFORMATION SUBMITTED WAS A COPY OF FLORIDA PRODUCT |
| APPROVAL FL282-R1.THIS PRODUCT APPROVAL IS FOR |
| ANOTHER TILE MANUFACTURER AND THERE WAS NO NOA |
| SUBMITTED WITH IT. PROVIDE 2 COPIES OF COMPLETE AND |
| CORRECT INFORMATION. |
| |
| 3- ROOF TILE FASTENING WAS NOT PROVIDED AS REQUESTED ON |
| PREVIOUS CHECKLIST.IF USING POLYFOAM, THEN PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.IS |
| USING SCREWS OR NAILS CLEARLY IDENTIFY WHICH TYPE AND |
| NUMBER TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL |
| AND DESIGN PRESSURES. |
| |
| 4- NOTICE OF COMMENCEMENTSUBMITTEDEXPIRED ON |
| 12/24/2006. NEED TO PROVIDE NEW NOTICE OF COMMENCEMENT |
| AS REQUIRED BY SEC. 713.13 FLORIDA STATUTES. |
| |
| 5- PERMIT APPLICATION HAS THE GENERAL CONTRACTOR AS THE |
| OWNER.GENERAL CONTRACTOR IS NOT THE OWNER.THESE ARE |
| PUBLIC RECORDS AND THEY NEED TO HAVE CORRECT OWNER'S |
| INFORMATION.PLEASE PROVIDE NEW PERMIT APPLICATION |
| WITH CORRECT INFORMATION |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |