2007-01-31 08:00:45 
  
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA STATUTES ,
 471.003, ALLOWING THE CONTRACTOR TO DRAW THEIR OWN
 PLANS. THE EXEMPTION INDICATES THE CONTRACTOR THAT IS
 INSTALLING THE WORK IS THE ONE COVERED UNDER THE
 EXEMPTION, 471.003(H).IN THE CASE OF THE ELECTRICAL
 PLANS , PLEASE HAVE THAT CONTRACTOR SUBMIT PLANS.
  
 2} IT IS UNCLEAR IF THE SERVICE IS BEING REPLACED,
 UPGRADED OR EXISTING. IF NEW, PLEASE SUBMI TA RISER
 DIAGRAM PER 215.5 AND PROVIDE AIC RATINGS FOR SAME PER
 110.9 & 10.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 4} THE ELECTRICALPANEL LOCATED IN THE KITCHEN MUST
 COMPLY WITH THE CLEARANCE REQUUIREMENTS OF 110.26, THAT
 INCLUDES THE PROXIMETY TO THE COUNTER.
  
 5} PER 210.8(A)(6) ALL COUNTERTOP RECEPTACLES IN THE
 KITCHEN MUST BE GFCI PROTECTED.
  
 6} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  