2007-01-31 08:00:45 | |
| |
| |
| NONCOMPLIANT |
| |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC AS |
| AMENDED. THIS ARTICLE ALSO IS AN EXTRACTION FROM THE |
| EXEMPTION IN CHAPTER 471 OF THE FLORIDA STATUTES , |
| 471.003, ALLOWING THE CONTRACTOR TO DRAW THEIR OWN |
| PLANS. THE EXEMPTION INDICATES THE CONTRACTOR THAT IS |
| INSTALLING THE WORK IS THE ONE COVERED UNDER THE |
| EXEMPTION, 471.003(H).IN THE CASE OF THE ELECTRICAL |
| PLANS , PLEASE HAVE THAT CONTRACTOR SUBMIT PLANS. |
| |
| 2} IT IS UNCLEAR IF THE SERVICE IS BEING REPLACED, |
| UPGRADED OR EXISTING. IF NEW, PLEASE SUBMI TA RISER |
| DIAGRAM PER 215.5 AND PROVIDE AIC RATINGS FOR SAME PER |
| 110.9 & 10. |
| |
| 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| RESIDENTIAL FLORIDA BUILDING CODE. |
| |
| 4} THE ELECTRICALPANEL LOCATED IN THE KITCHEN MUST |
| COMPLY WITH THE CLEARANCE REQUUIREMENTS OF 110.26, THAT |
| INCLUDES THE PROXIMETY TO THE COUNTER. |
| |
| 5} PER 210.8(A)(6) ALL COUNTERTOP RECEPTACLES IN THE |
| KITCHEN MUST BE GFCI PROTECTED. |
| |
| 6} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| 106.3.5.4(8) FBC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| WILLIAM R. TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| CONSTRUCTION SERVICES DEPARTMENT |
| 561) 805-6718 |