2007-02-23 13:47:02 | DENIED BY BUILDING |
| |
| 1) PLANS ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THEM. FBC* 106. |
| |
| 2) FBC * 106.1.1 REQUIRES CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 3) FBC * 106.1.3 QUALITY OF BUILDING PLANS. BUILDING |
| PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| |
| 4) FBC R312 AND FBC CHAPTER 11 REQUIRES AT LEAST ONE |
| BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE |
| BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH |
| A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING. |
| HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE |
| LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF |
| NOT LESS THAN 29 INCHES (737 MM). NEW MASTER BATH IS |
| REQUIRED TO COMPLY. |
| |
| 5) PLANS NEED TO SPECIFY THE WINDOW TYPE (I.E. SINGLE |
| HUNG, FIXED, ETC.), LOCATION OF EACH, ETC. AND WHICH |
| ONES ARE BEING REPLACED. |
| |
| 6) SPECIFY WHICH EXTERIOR DOORS ARE BEING REPLACED. |
| |
| 7) PLANS NEED TO SPECIFY THE LOCATIONS WHERE THE |
| DRYWALL IS BEING REPLACED. IF ALL THE WALLS AND CEILING |
| DRYWALL IS BEING REPLACED SPECIFY THAT ON THE PLANS. |
| |
| 8) PLANS NEED TO SPECIFY WHICH WALLS ARE NEW AND WHICH |
| ARE EXISTING. |
| |
| 9) PLANS NEED TO SPECIFY THE R-VALUE OF THE INSULATION |
| AND THE LOCATIONS OF WHERE EACH TYPE IS BEING |
| INSTALLED. |
| |
| 10) ENERGY CALC. FORM SPECIFIES EXTERIOR MASONRY WALLS |
| WITH R-11 INSULATION. TYPICALLY MASONRY WALLS ARE |
| INSULATED WITH R-5. SPECIFY HOW THE EXTERIOR MASORY |
| WALLS ARE BEING INSULATED TO ACHIEVE R-11. |
| |
| 11) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| STORM PANELS. SPECIFY THE FASTENER TYPE AND SPACING, |
| THE CONNECTION TYPE, THE EDGE DISTANCE, WIND PRESSURE, |
| SEPARATION DISTANCE, SPANS, ETC. CIRCLE THE APPROPRIATE |
| ITEMS ON THE NOA AND FILL OUT ATTACHED INSTALLATION |
| SCHEDULE OR PROVIDE ONE OF YOUR OWN |
| |
| 12) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW |
| MULLIONS. |
| |
| |
| 13) ON THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF |
| SYSTEM INDICATE WHICH ONE OF THE APPROVED SYSTEMS WILL |
| BE INSTALLED. SEE PAGES 9-31 OF NOA. INDICATE THE |
| FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED |
| TO INSTALL THE SYSTEM. IF ENHANCED FASTENING IS |
| REQUIRED TO INCREASE THE DESIGN PRESSURES AT THE |
| PERIMETER AND CORNER AREAS, SUBMIT RAS 117 CALCULATIONS |
| AS REQUIRED BY LIMITATION #7. SEE PAGE 32. |
| |
| 14) THE FL COVER SHEET SUBMITTED FOR THE GAF MODIFIED |
| ROOF SYSTEM IS NOT THE CORRECT ONE. THE CORRECT ONE IS |
| FL 617-R1. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |