Plan Review Notes For Permit 07010734 |
Permit Number |
07010734 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-07 14:57:06 | DENIED; | | 1. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3" | | FBC-2004 PLUMBING SECTION 406.3. A CLEANOUT IS REQUIRED | | AT 48" AFF. | | 2. THE W/M MUST DISCHARGE DOWN STREAM OF THE BATHROOM | | GROUP. SECTION 909.1. AND VENT REQUIRED. | | 3. THE WET VENT FOR THE BATHROOM IS REQUIRED TO BE 3" | | SEE SIZING TABLE 909.3 AND TABLE 709.1 TO SIZE FIXTURES | | THE FIXTURE UNITS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|