2007-02-21 18:07:38BUILDING REVIEW FOURTH CHECKLIST:
 1- GENERAL LIMITATION #7 ON FLAT ROOF SYSTEM NOA
 06-0410.06 SUBMITTED REQUIRESRAS 117 NAIL ENHANCING
 CALCULATIONS FOR PERIMETER AND CORNER AREAS TO BE DONE
 AND SIGNED,SEALED BY AN ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT. PROVIDE SUCH CALCULATIONS
 AS REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA SUBMITTED.
  
 2-A)IF SUBMITTING CALCULATIONS DONE BY ROBERT
 NIEMINEN, PE, THEN THEY NEED TO HAVE ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 B) PROPOSED SPACING FOR NAIL ENHANCING AT PERIMETER
 AREA(PAGE 2 OF 2) DOESN'T MEET REQUIRED SPACING.
 PROVIDE ACTUAL RAS 117 CALCULATIONS TO SHOW SPACING.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) IF USING SUBMITTED ENGINEER'S REPORT, THEN COMPLY
 WITH LIMITATIONS OF USE #D AND CONCLUSIONS.NEED
 WITHDRAWAL TESTING FOR BASE SHEET FASTENERS AND
 QUALIFIED PROFESSIONAL TO DETERMINE BUILDING EXPOSURE
 CATEGORY AND ENCLOSURE CONDITIONS (SEE PAGE 3 OF 3).
  
 3- INFORMATION SHOWN ON HIGH VELOCITY HURRICANE ZONE
 PERMIT APPLICATION DOESN'T MATCH ENGINEER REPORT
 SUBMITTED.SEE DESIGN PRESSURES AND LAPWIDTH.ON
 THE OTHER HAND, THIS FORMIS NOT REQUIRED IN THIS
 MUNICIPALITY.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712