Plan Review Notes For Permit 07010690 |
Permit Number |
07010690 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-29 08:09:31 | BUILDING REVIEW THIRD CHECKLIST: | | 1- PRODUCT APPROVAL NOA #03-0130.08 EXPIRED ON | | 09/13/06. PROVIDE CURRENT NOA. | | | | 2- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING | | PERMITS. SEE ATTACHED COPY OF CITY POLICY. | | | | 3- IF SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET | | FASTENING OPTIONS, THEN SPECIFY WHICH OPTION IS GOING | | TO BE USED. SEE CITY POLICY FOR ROOFING PERMITS. | | | | 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #7, THEN PROVIDE RASS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS. | | CALCULATIONS SHALL BE SIGNED AND SEALED BY ARCHITECT, | | ENGINEER OR REGISTERED ROOFING CONSULTANT. SEE GENERAL | | LIMITATION #7 ON PAGE 45 OF 45 OF NOA SUBMITTED. | | | | 5- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA | | BECAUSE ASSEMBLY CAN'T BE ENHANCED TO INCREASE THE | | DESIGN PRESSURES. SEE GENERAL LIMITATION #9 ON PAGE 45 | | OF 45 OF NOA SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|