2007-01-29 08:09:31BUILDING REVIEW THIRD CHECKLIST:
 1- PRODUCT APPROVAL NOA #03-0130.08 EXPIRED ON
 09/13/06. PROVIDE CURRENT NOA.
  
 2- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY OF CITY POLICY.
  
 3- IF SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET
 FASTENING OPTIONS, THEN SPECIFY WHICH OPTION IS GOING
 TO BE USED. SEE CITY POLICY FOR ROOFING PERMITS.
  
 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RASS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS.
 CALCULATIONS SHALL BE SIGNED AND SEALED BY ARCHITECT,
 ENGINEER OR REGISTERED ROOFING CONSULTANT. SEE GENERAL
 LIMITATION #7 ON PAGE 45 OF 45 OF NOA SUBMITTED.
  
 5- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA
 BECAUSE ASSEMBLY CAN'T BE ENHANCED TO INCREASE THE
 DESIGN PRESSURES. SEE GENERAL LIMITATION #9 ON PAGE 45
 OF 45 OF NOA SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712