Plan Review Notes
Plan Review Notes For Permit 07010690
Permit Number 07010690
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-11 16:47:21BUILDING REVIEW CHECKLIST:
 1- SEE ATTACHED COPY OF CITY POLICY FOR ROOFING
 PERMITS. NEED THE FOLLOWING:
 A) FLAT ROOF SYSTEM NEED TO PROVIDE TECHNICAL REPORT
 THAT WAS SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL1213.
 VISIT WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL RELEVANT
 INFORMATION.ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGES WERE SUBMITTED. SEE ATTACHED COPY OF CITY
 POLICY.
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL FL1213 FOR 2004
 CODE VERSION. ONE SUBMITTED IS FOR 2001.
  
 C) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING
 TO BE INSTALLED AS REQUIRED BY CITY POLICY.
  
 D) ON SELECTED ASSEMBLY CLEARLY IDENTIFY WHICH BASE
 SHEET FASTENING OPTION IS GOING TO BE INSTALLED. SEE
 CITYPOLICY.
  
 E) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT CORNER AND PERIMETER AREAS. SEE
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA. CALCULATIONS
 NEED TO BE SIGNED AND SEALED BY ARCHITECT, ENGINEER OR
 REGISTERED ROOFING CONSULTANT.
  
 F) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA
 BECAUSE OF THE REQUIRED DESIGN PRESSURES.
  
 2- ROOF SHINGLES. PROVIDE COMPLETE TECHNICAL REPORT.
 ONLY THE FLORIDA PRODUCT APPROVAL FL3663 COVER PAGES
 WERE SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712