Plan Review Notes For Permit 07010601 |
Permit Number |
07010601 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-20 11:40:44 | DENIED; | | 1. FBC-2004 BUILDING CHAPTER 11 SECTION 11-4.1.3(11) | | TOILET FACILITIES, TOILET ROOMS SHALL BE ACCESSIBLE SEE | | SECTIONS 11-4.22.1 THRU 11-4.22.7. SHOW DETAIL ON PLANS | | WITH ALL REQUIRED MEASUREMENTS. | | 2. FBC PLUMBING TABLE 403.1 MINIMUM PLUMBING | | FIXTURES(2B) REQUIRES A DRINKING FOUNTAIN THATMUST | | COMPLY WITH HANDICAP CODE SECTION 11-4.1.3(10) AND | | SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON | | PLANS. | | 3.BREAKSINK TO COMPLY WITH 11-4.24.1 THRU 11-4.24.7 | | SHOW DETAIL ON PLANS. | | 4. SHOW CLEAR FLOOR SPACE AND TURNING RADIUS ON FLOOR | | PLAN. | | 5. WATER ISOMETRIC; IF DISHWASHER OR ICE MAKER ARE | | INSTALLED WATER HAMMER ARRESTORS ARE REQUIRED PER | | SECTION 604.9. SHOW ON DIAGRAM AND LIST TYPE ON PLANS. | | 6.THERMAL EXPANTION CONTROL IS REQUIRED ON WATER HEATER | | PER SECTION 607.3. | | 7.SHOW A DETAIL OF WATER HEATER THAT SHOWS A HEATER | | PAN, DRAIN AND TERMINATION OF HEATER PLAN DRAIN PER. | | SECTIONS 504.6.2, 504.7.1 AND 504.7.2. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|