Plan Review Notes
Plan Review Notes For Permit 07010601
Permit Number 07010601
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-20 11:40:44DENIED;
 1. FBC-2004 BUILDING CHAPTER 11 SECTION 11-4.1.3(11)
 TOILET FACILITIES, TOILET ROOMS SHALL BE ACCESSIBLE SEE
 SECTIONS 11-4.22.1 THRU 11-4.22.7. SHOW DETAIL ON PLANS
 WITH ALL REQUIRED MEASUREMENTS.
 2. FBC PLUMBING TABLE 403.1 MINIMUM PLUMBING
 FIXTURES(2B) REQUIRES A DRINKING FOUNTAIN THATMUST
 COMPLY WITH HANDICAP CODE SECTION 11-4.1.3(10) AND
 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON
 PLANS.
 3.BREAKSINK TO COMPLY WITH 11-4.24.1 THRU 11-4.24.7
 SHOW DETAIL ON PLANS.
 4. SHOW CLEAR FLOOR SPACE AND TURNING RADIUS ON FLOOR
 PLAN.
 5. WATER ISOMETRIC; IF DISHWASHER OR ICE MAKER ARE
 INSTALLED WATER HAMMER ARRESTORS ARE REQUIRED PER
 SECTION 604.9. SHOW ON DIAGRAM AND LIST TYPE ON PLANS.
 6.THERMAL EXPANTION CONTROL IS REQUIRED ON WATER HEATER
 PER SECTION 607.3.
 7.SHOW A DETAIL OF WATER HEATER THAT SHOWS A HEATER
 PAN, DRAIN AND TERMINATION OF HEATER PLAN DRAIN PER.
 SECTIONS 504.6.2, 504.7.1 AND 504.7.2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695