Plan Review Notes For Permit 07010601 |
Permit Number |
07010601 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-01-24 16:56:29 | *****DENIED***** | | | | | | 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, | | SHALL BE REFERENCED. | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INERFERE OR | | HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE. | | | | 05.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE. | | | | 06.FIRE ALARM STROBE NEEDED IN THE CONFERENCE ROOM. | | | | 07.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS | | MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE SHOP | | DRAWINGS/PLANS AND PERMIT WILL BE REQUIRED. | | | | 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR | | WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | AND IN ALL OTHER AREAS. | | | | 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE | | EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE | | REQUIREMENT. | | | | 10.PROVIDE THE TRAVEL DISTANCE TO THE EXIT MEASURED | | ON THE FLOOR OR OTHER WALKING SURFACE AS PER NFPA 101, | | 7.6 | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|