2007-03-13 13:02:22*****UNSAT*****
  
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH
 STILL NEED TO BE ADDRESSED:
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE
 CLASSIFICATION,ADD "NFPA 101 2003 EDITION"
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON
 SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241"
  
 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 -
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND
 SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE
 SPECIFY
  
 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF
 FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM
 BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL
 BE LOCATED IN THE TENANT SPACE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE
 PLAN) EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722