2007-03-13 13:02:22 | *****UNSAT***** |
| |
| COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN |
| SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH |
| STILL NEED TO BE ADDRESSED: |
| |
| |
| 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, |
| SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE |
| CLASSIFICATION,ADD "NFPA 101 2003 EDITION" |
| |
| 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON |
| SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241" |
| |
| 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR |
| WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 - |
| INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND |
| SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE |
| SPECIFY |
| |
| 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE |
| EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE |
| REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF |
| FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM |
| BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL |
| BE LOCATED IN THE TENANT SPACE. |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE |
| PLAN) EACH ITEM WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |