2007-01-20 14:24:53DENIED;
 1.FBC-2004 PLUMBING TABLE 403.1 MINIMUM PLUMBING
 FIXTURES. PLEASE REFORANCE WHERE BATHROOMS AND DRINKING
 FOUNTAIN ARE LOCATED.
 2.KITCHENETTE SINK MUST MEET FBC-2004 BUILDING CHAPTER
 11 HANDICAP ACCESSIBLITY. SEE SECTIONS 11-4.24.2 THRU
 11-4.24.7. SHOW DETAIL ON PLANS WITH ALL MEASUREMENTS
 REQUIRED.
 3.DOOR CANNOT SWING INTO THE CLEAR FLOOR SPACE OF THE
 SINK.