Plan Review Notes
Plan Review Notes For Permit 07010598
Permit Number 07010598
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-24 15:20:16*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INERFERE OR
 HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE.
  
 5.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
 6.FIRE ALARM STROBE NEEDED IN THE CONFERENCE ROOM.
  
 7.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE SHOP
 DRAWINGS/PLANS AND PERMIT WILL BE REQUIRED.
  
 8.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.
  
 9.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722