Plan Review Notes
Plan Review Notes For Permit 07010596
Permit Number 07010596
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-04 18:26:27**UNSAT***
  
  
 1)PLEASE KNOW TO QUALIFY UNDER "MANAGMENT" MUST HAVE
 "QUALIFIED PERSONNEL" AS DEFINED ON THE NEC ART 100.
  
 2) MAXIMUM TIME FOR OC TYPE DEVICES TO BE 30MINS PER
 13-415.1.ABC.1.1, NOT STATED ON PLANS.
  
 3) PLEASE SEE NO ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS, LIGHTING POWER DENSITES SHOWN OR
 SUBMITTED.
 13-415.1.AB.1.1, 13-415.2
 ** PLEASE SEE THE PLANS WERE STAMPED AND WILL BE COMING
 BACK FOR OTHER TRADES AS THE ARCHITECT DID NOT DATE
 PLANS.
 PLEASE ADDRESS COMMENT #3 BY WAY OF PLANS OR SEPARATE
 AS SHEETS WERE STAMPED IN ERROR.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]