Date |
Text |
2007-01-15 08:41:11 | PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO |
| INCOMING AWAITING SPACE ON THE BOB BOARD. |
| |
2007-01-15 08:41:04 | ** UNSAT ** |
| |
| 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS |
| REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL. |
| THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE |
| ALREADY, HOWEVER PLEASE SEE MISSING. |
| |
| PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| RELEVANT. |
| 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| (NEC). (THE 2005 NEC IS SHOWN) |
| 2002 NFPA-72 |
| 2003 NFPA-101. |
| |
| 2) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON |
| PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO |
| ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE |
| SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS, |
| CONFERENCE RM ETC. |
| THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED |
| BEFORE INSPECTION FOR FINAL. |
| 106.1.2, 106.3.5.1.2 |
| NEC 408.4, 310.16, 240.4 FOR VERIFICATION. |
| |
| 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER |
| 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2. |
| THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE |
| DESIGNER OF RECORD. |
| PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES |
| TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION |
| ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE |
| PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS. |
| PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER |
| 13. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS, |
| SCHEDULING, DEVICES AND TYPES OF DEVICES. |
| PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE |
| DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR |
| TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW |
| DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME |
| IDENTIFICATION. |
| PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE |
| MISSING AT ENTRANCE INTO SPACE. |
| PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE |
| EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS, |
| HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE |
| JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE |
| LOAD SIDE OF THESE DEVICES. |
| PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW, |
| A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT |
| THIS TIME. |
| |
| |
| 4) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS |
| NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS |
| THE COVERS ARE NOT LOCKABLE? |
| PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS |
| UNDER MANAGEMENT OF QUALIFIED PERSONNEL. |
| 240.24, (A), (B), (C). |
| |
| |
| 5) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE |
| SHOWN AT 125% FOR CONTINUOUS LOADS. |
| 215.3, 230.42 ETC. |
| 220.12, 220.14, 220.43, 220.44 ETC. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |