Plan Review Notes
Plan Review Notes For Permit 07010596
Permit Number 07010596
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-15 08:41:11PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO
 INCOMING AWAITING SPACE ON THE BOB BOARD.
  
2007-01-15 08:41:04** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS
 REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL.
 THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE
 ALREADY, HOWEVER PLEASE SEE MISSING.
  
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC). (THE 2005 NEC IS SHOWN)
 2002 NFPA-72
 2003 NFPA-101.
  
 2) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO
 ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE
 SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS,
 CONFERENCE RM ETC.
 THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED
 BEFORE INSPECTION FOR FINAL.
 106.1.2, 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 FOR VERIFICATION.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER
 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS,
 SCHEDULING, DEVICES AND TYPES OF DEVICES.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR
 TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW
 DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME
 IDENTIFICATION.
 PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE
 MISSING AT ENTRANCE INTO SPACE.
 PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE
 EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS,
 HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE
 JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE
 LOAD SIDE OF THESE DEVICES.
 PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW,
 A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
  
 4) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS
 NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS
 THE COVERS ARE NOT LOCKABLE?
 PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS
 UNDER MANAGEMENT OF QUALIFIED PERSONNEL.
 240.24, (A), (B), (C).
  
  
 5) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE
 SHOWN AT 125% FOR CONTINUOUS LOADS.
 215.3, 230.42 ETC.
 220.12, 220.14, 220.43, 220.44 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]