2007-01-22 09:02:48 | BUILDING PLAN REVIEW |
| PERMIT: 07010596 |
| ADD: 2247 PALM BCH LAKES # 205 |
| CONT: ANDREA CONSTRUCTION |
| TEL: (561)358-4797 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, |
| SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| POSTING OF THE |
| NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE |
| THE |
| FIRST INSPECTION. |
| |
| 3) 110.2* W. P. B. ADMINISTRATIVE |
| CODE, INFORMATION THAT IS REQUIRED FOR |
| RECORD KEEPING & FOR CERTIFICATE OF |
| OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| 2004FBC/ 2006 REVISIONS. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) LEVEL OF ALTERATION: LEVEL 1.2OR 3? |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| G) NUMBER OF FLOORS |
| |
| 4) SHEET A-101, DOES NOT INDICATE THE SIZE OF THE |
| DOORS, |
| 11-4.13.5 DOORWAYS, MINIMUM |
| CLEAR WIDTH: DOORWAY SHALL HAVE A MINI- |
| MUM CLEAR OPENING OF 32" WITH THE DOOR |
| OPEN 90 DEGREES, MEASURED BETWEEN THE |
| FACE OF THE DOOR AND THE OPPOSITE STOP. |
| |
| 5)THE KITCHENETTES SINK LOCATION DOESN'T PROVIDE |
| CLEAR FLOOR SPACE; |
| SINKS: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW |
| FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| ACCESSIBLE ROUTE |
| AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) |
| UNDERNEATH THE SINK. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |