Plan Review Notes
Plan Review Notes For Permit 07010582
Permit Number 07010582
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-02 07:21:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)THE ANCHOR SCHEDULE STATES "NA" FOR ANCHOR SPACING
 FOR ROLLUP SHUTTERS.SEE SHEET 3 OF 21 OF THE PRODUCT
 APPROVAL WHERE YOU HAVE INDICATED 6IN OC.THE PURPOSE
 OF NA IS NOT CLEAR.PLEASE INCLUDE PROPOSED ANCHORING
 INFORMATION SO THAT CODE COMPLIANCE CAN BE DETERMINED.
  
 2.)ON THE SHUTTER SCHEDULE, THE ACCORDION SPANS ARE
 LESS THAN THE SHUTTER SIZES.PLEASE DIRECT ME TO THE
 DETAIL WHICH WOULD SHOW THE BLADE SMALLER THAN THE
 SHUTTER.
  
  
  