Plan Review Notes
Plan Review Notes For Permit 07010560
Permit Number 07010560
Review Stop M
Sequence Number 2
Notes
Date Text
2007-02-02 08:51:13REVISION TO MECHANICAL PLANS
 *** DENIED ***
 1) LETTER FROM G. C. TO REMOVE ENGINEER FROM MECHANICAL
 PLANS, (A) MUST BE ON COMPANY LETTER HEAD, (B) MUST
 REFERENCE AND SHOW BUILDING PERMIT NUMBER, AND (C)
 SIGNATURE MUST BE NOTARIZED.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2
  
 3) PLEASE SIGN PLANS.ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.