2007-01-23 07:00:23 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} INDICATE THE FEEDER OCP AND CONDUCTOR SIZE.
  
 2} INDICATE THE RATING FOR THE DISCONNECT AT THE LIFT.
  
  
 3} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.