Date |
Text |
2007-07-07 19:28:22 | 2007-07-07 19:28:22 |
| *** NOTE ADDED ** |
| |
| 1) NOTE THIS COMMENT IS FOR THE LANDSCAPE PLANS AND |
| DESIGNER OF RECORD FOR THESE SHEETS. |
| PLEASE SEE THE SEAL IN USE ON LANDSCAPE PLANS IS |
| REQUIRED TO MEET FAC 61G1-16.002. THIS IS REQUIRED |
| WHETHER OR NOT COMMENT IS MADE BY OTHER. |
| THIS IS A NEW COMMENT AND WAS NOTICE WHEN PLANS WERE |
| BEING ROLLED. PLEASE SEE ZONING FOR POSSIBLE COMMENTS |
| EITHER ON PREVIOUS OR PRESENT REVIEW. |
2007-07-07 19:08:06 | 2007-07-07 19:08:06 |
| **** UNSAT3RDREVIEW **** |
| |
| ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE |
| TWO PREVIOUS REVIEWS WHICH STILL NEED TO BE ADDRESSED. |
| |
| ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON |
| CHANGES AND REVISIONS NOW MADE TO PLANS WHICH WERE NOT |
| ON PREVIOUS REVIEWED PLANS. |
| |
| |
| 1) NOTE:PLEASE SEE BOTH PREVIOUS REVIEWS REQUESTED |
| FOR THE REQUIRED CODES TO BE STATED ON BOTH THE |
| ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE THE ONLY |
| CHANGE WAS MADE TO THE ARCHITECTURAL SHEETS AND THE |
| ELECTRICAL SHEETS STILL CONTAIN THE SAME GENERAL |
| STATEMENT. |
| PLEASE SEE THAT RELEVANT CODES UNDER A DESIGN OF ANY |
| PROJECT SHALL BE STATED ON PLANS AS REQUIRED UNDER THE |
| FBC. |
| PLEASE BE SURE THE FOLLOWING IS STATED ON THE |
| ELECTRICAL SHEETS: |
| 2005 NFPA-70 (NEC |
| 2003 NFPA-101 LIFE SAFETY CODE |
| 2002 NFPA-72 |
| 2004 FBC W/2006 REVISIONS. |
| PLEASE STATE THESE CODE ON E COVER SHEETS OR ANY OTHER |
| E-SHEET(S) WHERE NOTES ARE PRESENT REFLECTING THE CODE |
| |
| |
| 2) NOTE: PLEASE SEE THE PREVIOUS TWO REVIEWS REQUESTED |
| COMPLIANCE TO FBC CHAPTER 13. THERE WERE SUBSTANTIAL |
| CHANGES WHICH WENT INTO EFFECT ON OCTOBER 1ST, 2005. |
| PLEASE SEE NOT SYSTEM IS PROPOSED, ONLY PLANS NOW |
| INDICATE A SYMBOL IN AREAS FOR *MOTION DETECTORS* |
| PLEASE SEE NO TIMES OR INFORMATION WAS PROVIDED FOR |
| THESE NEW DEVICES AS NOTED PREVIOUSLY. NO DETAIL ON |
| WIRING OF THESE DEVICES AS LIGHTING IS STILL SHOWN |
| CIRCUITED BACK TO THE MAIN PANEL. |
| PLEASE SEE NOT ALL AREAS SHOW MOTION DETECTORS OR |
| OCCUPANCY DEVICES. PLEASE SPECIFY THESE DEVICES. PLEASE |
| KNOW RANGES ON MOTION DEVICES ONLY ARE DIFFERENT AND |
| MAY OR MAY NOT PROVIDE THE NEEDED COVERAGE. PLEASE SEE |
| OTHER COMMENT WITH RESPECT TO STAIRS ON MOTION |
| DETECTORS. |
| PLEASE SEE SEPARATE SPACES WHICH REQUIRE DEVICES YET |
| PLANS DO NOT INDICATE ANY DEVICES FOR THESE AREAS. |
| PLEASE SEE THERE ARE MAXIMUM TIMES STATED IN THE FBC |
| DEPENDING ON THE TYPES OF DEVICES CHOSEN. (OS TYPES |
| 30MINS)(TIMER TYPES 4HRS) THIS ALL DEPENDS ON DESIGN OF |
| DEVICES ETC. |
| PLEASE SEE THE SAME ENERGY CALCULATIONS WERE SUBMITTED |
| BACK. PLEASE SEE THE RESPONSE MENTIONS HAVE BEEN |
| PROPERLY SUBMITTED, HOWEVER PLEASE SEE NO INFORMATION |
| PER 13-415.2 COULD BE FOUND ON PLANS AND OTHER |
| DOCUMENTS SUBMITTED. PLEASE SEE THE FIXTURES AS SHOWN |
| ON PLANS DO NOT ALL CORRELATE WITH THE FIXTURE LEGEND |
| AND NO PERFORMANCE CALCULATIONS WERE LOCATED BASED ON |
| THE FIXTURES ON PLANS AND SQ FT OF PROJECT ON HOW THE |
| NUMBER OF 1.0 W/SF IS MET. |
| THE DESIGN TOTAL COMPARED TO THE DESIGN ALLOWANCE BASED |
| ON THE SECTION 13-415.2.C.1, 13-415.2.C. |
| 13-415.2.ABC.1.3 |
| PLEASE SEE AS THE SAME ENERGY CALCULATIONS FOR METHOD C |
| WAS SUBMITTED BACK; PLEASE SEE THESE ARE STILL NOT |
| SEALED AS REQUIRED AND PREVIOUSLY REQUESTED. PLEASE SEE |
| 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND |
| 13-415.1.ABC.1.3 (WHERE APPLICABLE ON .1.3).PLEASE SEE |
| 13-103.1.1.1 WHICH REQUIRES THESE TO BE *SIGNED, DATED |
| AND SEALED* BY THE DESIGN PROFESSIONAL OF RECORD AND |
| RESPONSIBLE FOR THE DOCUMENTS. |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED |
| PHOTO-METRICS AND ANY CONTROLS TO MEET BOTH THE FBC AND |
| NFPA-101 FOR DEVICES CHOSEN. |
| PLEASE SEE THE PLANS NOW INDICATE ONLY ONE DEVICE ON |
| EACH LEVEL FOR CONTROL OF EGRESS LIGHTING. PLEASE SEE |
| 7.9.2.2 OF THE LIFE SAFETY CODE WHICH WAS GIVEN ON BOTH |
| OF THE PREVIOUS REVIEWS. |
| FBC 1006.1.2, LS101 7.8.1.2.2 |
| PLEASE ADJUST. |
| |
| 4) NOTE: PLEASE SEE FIRST REVIEW COMMENTS WHICH GAVE |
| NOTES FOR REQUIRED DEDICATED CIRCUITS FOR ELEVATOR |
| ROOMS, EQUIPMENT ETC. THE RESPONSE WAS THE EQUIPMENT |
| ROOM WAS TO HAVE DEDICATED CIRCUITS ETC AND THIS WAS |
| DONE. PLEASE SEE 620.24 HOWEVER AS THIS REQUIRES |
| DEDICATE BRANCH CIRCUIT FOR PIT LIGHTS AND RECEPTACLES. |
| PLEASE SEE THE LIGHTING IS STILL SHOWN ON THE SAME |
| CIRCUIT AS THE LIGHTING ON FIRST FLOOR. |
| |
| 5) NOTE: PLEASE SEE THAT SOME LOAD CALCULATIONS FOR |
| SERVICE ARE NOW BEING SUBMITTED FOR THE FIRST TIME FOR |
| REVIEW. PLEASE SEE NO LOAD SUMMARY ON HOW LOADS WERE |
| DERIVED WAS SUBMITTED. |
| PLEASE SEE CONTINUOUS LOADS AS REQUIRED ARE STILL NOT |
| SHOWN AT 125%. |
| PLEASE SUBMIT LOAD CALCULATIONS BASED ON FUTURE LOADS |
| AND CURRENT KNOWN |
| PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, |
| 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS |
| PREVIOUSLY NOTED. |
| PLEASE CLARIFY WHERE THE *85%* AS SHOWN AS A DE-RATING |
| FOR * EQUIPMENT* COMES FROM BASED ON THE NEC. PLEASE |
| SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE AND EACH |
| OF THE PANELS AS BEING SHOWN EVEN THOSE BEING SET ASIDE |
| FOR FUTURE USE. PLEASE SEE THE ONLY PANEL SHOWN WHICH |
| IS THE NHP AND THIS DOES NOT INCLUDE A LOAD SUMMARY OR |
| HOW THE SERVICE WAS SIZED OR CORRECT LOAD CALCULATIONS |
| FOR THIS PANEL OR SERVICE. |
| PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR |
| CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| NOT BE DETERMINED AT THIS TIME. |
| PLEASE SEE ALL OF 220. |
| PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| LOADS AND LARGEST MOTORS LOADS AT 125%. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| |
| 6) NOTE: PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT |
| COMPLETE. |
| PLEASE SEE NO INFORMATION FOR ANY OF THE PROPOSED MAINS |
| IS SHOWN. ONLY ONE OF THE MAINS INDICATES IT WILL BE |
| 800AMPS. |
| PLEASE SEE NO AIC RATINGS FOR EACH OF THE SERVICE |
| EQUIPMENT AND MAIN WAS SUBMITTED. SOME AIC CALCULATIONS |
| THESE WAS SUBMITTED. 110.9 |
| PLEASE SEE NO MAINS AS REQUIRED PER 230.70, 230.71, |
| 230.72, 230.76 AND 230.79 ETC WAS SHOWN. |
| IN FACT PLEASE SEE THE RESPONSE LETTER NOW MENTIONS |
| SPECIFICALLY THAT A NEW SHUNT TRIP AND SHUNT TRIP |
| BREAKERS WAS ADDED. THE RISER NOW SHOWS THIS AND AS |
| PREVIOUSLY STATED IN BOTH PREVIOUS REVIEWS MAIN MUST |
| MEET 230.76 AND 230.79. SHUNT TRIP BREAKERS AND SHUNT |
| TRIPS DO NOT MEET CODE. PLEASE KNOW THAT ALL MAINS AND |
| MEANS OF DISCONNECT MUST CONTAIN A MANUAL MEANS OF |
| DISCONNECT RATED FOR THE LOAD SERVED. |
| PLEASE SEE THE LOCATION OF THESE MAINS SHALL BE LOCATED |
| AT THE NEAREST POINT OF ENTRANCE INTO THE BUILDING. |
| THIS IS A LIFE SAFETY HAZARD AND PROPERTY HAZARD. IF |
| THERE IS A STRUCTURE FIRE FOR EXAMPLE AND THE ONLY WAY |
| TO SHUT OFF THE POWER TO THE BUILDING IS LOCATED CLOSE |
| TO THE CENTER OF THE BUILDING THIS WOULD NOT ONLY CAUSE |
| A DELAY IT WOULD ALSO CREATE A HAZARD TO FIRE |
| DEPARTMENT PERSONNEL IN AN EFFORT TO TURN OFF POWER. |
| PLEASE SEE THERE ARE NUMEROUS ITEMS NOT COMPLETED ON |
| RISER AT THIS TIME. |
| |
| ** AS A NOTE PANEL NHP IS GOING TO BE 800AMPS? |
| |
| 7) NOTE: PLEASE SEE THE RISER STILL DOES NOT INDICATE |
| THE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50. |
| PLEASE SEE THE RISER MENTIONS AND SHOWS ALL AS EXISTING |
| HOWEVER THIS IS NOT POSSIBLE AS THE RISER JUST ABOVE |
| WHICH SHOWS EXISTING CONDITIONS AND THIS DOES NOT |
| CORRELATE WITH THE NEW PROPOSED RISER. |
| HOW CAN THE GROUNDING ELECTRODE SYSTEM AS SHOWN BE |
| EXISTING WHEN THE RISER AS SHOWN IS NEW? |
| PLEASE ALSO SEE THAT 250.50 WHICH REQUIRES ALL FOOTER |
| STEEL ETC TO BE PART OF THE GROUNDING ELECTRODE SYSTEM. |
| PLEASE SEE THE ADDITION AND NEW FOOTER STEEL OR |
| BUILDING STEEL ETC IS REQUIRED TO BE PART OF THE |
| SYSTEM. |
| PLEASE SHOW NEW SYSTEM. |
| 250.50,250.54, 250.56 ETC. |
| PLEASE ALSO SEE AS PREVIOUSLY NOTED IN REVIEWS: THE |
| RISER IS STILL SHOWING *EQUIPMENT GROUNDING CONDUCTORS* |
| AHEAD OF THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT |
| PERMITTED. THIS CONDITION AS SHOWN WOULD CREATE |
| OBJECTIONABLE CURRENTS AS STATED IN 250.6. |
| PLEASE SEE 250.24 AS THIS REQUIRES BONDING AT THE FIRST |
| MEANS OF DISCONNECT. WHEN THE BONDING IS DONE AT THE |
| FIRST MEANS OF DISCONNECT AS REQUIRED PER 250.24 AND IF |
| AN *EQUIPMENT GROUNDING CONDUCTOR IS INSTALLED BEFORE |
| THE FIRST MEANS OF DISCONNECT THEN THIS WOULD BE |
| PARALLELING THE NEUTRAL. (OBJECTIONABLE CURRENTS) |
| PLEASE ADJUST RISER. |
| |
| 8) NOTE: PLEASE SEE ONLY ONE SET OF PLANS CONTAIN |
| SHEETS FOR A LIGHTNING PROTECTION SYSTEM. |
| PLEASE SUBMIT TWO COMPLETED SET OF PLANS ALONG WITH NEW |
| SHEETS FOR REVISED COMMENTS AS WELL AS LIGHTNING |
| PROTECTION SHEETS. |
| |
| 9) NOTE: PLEASE SEE PREVIOUS REVIEWS STATED A NOTE |
| WHICH SAID *PLEASE BE SURE TO CALL IF THERE ARE ANY |
| QUESTIONS OR COMMENTS WITH RESPECT TO THE TYPED |
| COMMENTS*. IT ALSO STATED * IF THERE ARE ANY COMMENT |
| WHICH ARE NOT CLEAR IN ANY WAY, NOT UNDERSTOOD OR NOT |
| TYPED IN A CLEAR MANOR, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER*. |
| PLEASE KNOW TO DATE NO CONTACT FROM THE DESIGNER OF |
| RECORD HAS BEEN MADE. |
| **PLEASE SEE PREVIOUS NOTES GAVE NOTICE TO FS |
| 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| COMPLIANCE. |
| PLEASE SEE SEVERAL OF THE CODE SECTIONS GIVEN ON ALL |
| PREVIOUS REVIEWS STILL REMAIN. PLEASE SEE AS REQUIRED |
| PER THE FLORIDA STATUTES 553.80(2)(B), A FEE HAS NOW |
| BEEN ASSESSED AS REQUIRED FOR SAID REPEAT COMMENTS. |
| THIS STATUTE APPLIES TO ANY OF THE SAME CODE COMPLIANT |
| COMMENTS REPEATED. |
| PLEASE SEE THE AMOUNT DUE BEFORE PLANS MAY BE |
| RESUBMITTED IS 4X TIMES THE PORTION OF THE BASE PERMIT |
| FEE ATTRIBUTED TO PLAN REVIEW. THE BASE PERMIT FEE WAS |
| $12,500 AT 30% IS $3,750 TIME FOUR.THIS FEE IS |
| $15,000.00. |
| THIS FEE IS REQUIRED BEFORE PLANS MAY BE SUBMITTED. ** |
| IT IS STRONGLY RECOMMENDED THAT A MEETING BE HELD |
| BETWEEN THE DESIGN TEAM AND THIS OFFICE ONCE ALL OF THE |
| REVIEWS HAVE BEEN COMPLETED AS THE STATUTE REQUIRES THE |
| FINE EACH TIME THEREAFTER AS WELL. |
| PLEASE KNOW THAT PLANS ARE BEING RETAINED BY THIS |
| OFFICE AND WILL BE PLACED WITH PLANS WHICH WERE |
| RETAINED FROM PREVIOUS REVIEWS. |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE |
| ALSO BEING RETAINED. |
| PLEASE KNOW IF THERE IS A CONFLICT BETWEEN THE DESIGN |
| TEAM OR DESIGNER WHICH IS NOT SETTLED ON A LOCAL LEVEL |
| THE PLANS WILL BE FORWARD TO THE FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS AND STATES LEGAL COUNSEL TO THE |
| BOARD FOR REVIEW. |
| THIS INFORMATION WILL BE FORWARDED TO THE ASSISTANT |
| BUILDING OFFICIAL MR. ROBERT BROWN. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-07-07 15:50:24 | 2007-07-07 15:50:24 |
| PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO |
| INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| IS COMPLETED. |