Plan Review Notes
Plan Review Notes For Permit 07010472
Permit Number 07010472
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-07 19:28:222007-07-07 19:28:22
 *** NOTE ADDED **
  
 1) NOTE THIS COMMENT IS FOR THE LANDSCAPE PLANS AND
 DESIGNER OF RECORD FOR THESE SHEETS.
 PLEASE SEE THE SEAL IN USE ON LANDSCAPE PLANS IS
 REQUIRED TO MEET FAC 61G1-16.002. THIS IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER.
 THIS IS A NEW COMMENT AND WAS NOTICE WHEN PLANS WERE
 BEING ROLLED. PLEASE SEE ZONING FOR POSSIBLE COMMENTS
 EITHER ON PREVIOUS OR PRESENT REVIEW.
2007-07-07 19:08:062007-07-07 19:08:06
 **** UNSAT3RDREVIEW ****
  
 ** PLEASE SEE THERE ARE STILL SEVERAL ITEMS FROM THE
 TWO PREVIOUS REVIEWS WHICH STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS NOW MADE TO PLANS WHICH WERE NOT
 ON PREVIOUS REVIEWED PLANS.
  
  
 1) NOTE:PLEASE SEE BOTH PREVIOUS REVIEWS REQUESTED
 FOR THE REQUIRED CODES TO BE STATED ON BOTH THE
 ARCHITECTURAL AND ELECTRICAL PLANS. PLEASE SEE THE ONLY
 CHANGE WAS MADE TO THE ARCHITECTURAL SHEETS AND THE
 ELECTRICAL SHEETS STILL CONTAIN THE SAME GENERAL
 STATEMENT.
 PLEASE SEE THAT RELEVANT CODES UNDER A DESIGN OF ANY
 PROJECT SHALL BE STATED ON PLANS AS REQUIRED UNDER THE
 FBC.
 PLEASE BE SURE THE FOLLOWING IS STATED ON THE
 ELECTRICAL SHEETS:
 2005 NFPA-70 (NEC
 2003 NFPA-101 LIFE SAFETY CODE
 2002 NFPA-72
 2004 FBC W/2006 REVISIONS.
 PLEASE STATE THESE CODE ON E COVER SHEETS OR ANY OTHER
 E-SHEET(S) WHERE NOTES ARE PRESENT REFLECTING THE CODE
  
  
 2) NOTE: PLEASE SEE THE PREVIOUS TWO REVIEWS REQUESTED
 COMPLIANCE TO FBC CHAPTER 13. THERE WERE SUBSTANTIAL
 CHANGES WHICH WENT INTO EFFECT ON OCTOBER 1ST, 2005.
 PLEASE SEE NOT SYSTEM IS PROPOSED, ONLY PLANS NOW
 INDICATE A SYMBOL IN AREAS FOR *MOTION DETECTORS*
 PLEASE SEE NO TIMES OR INFORMATION WAS PROVIDED FOR
 THESE NEW DEVICES AS NOTED PREVIOUSLY. NO DETAIL ON
 WIRING OF THESE DEVICES AS LIGHTING IS STILL SHOWN
 CIRCUITED BACK TO THE MAIN PANEL.
 PLEASE SEE NOT ALL AREAS SHOW MOTION DETECTORS OR
 OCCUPANCY DEVICES. PLEASE SPECIFY THESE DEVICES. PLEASE
 KNOW RANGES ON MOTION DEVICES ONLY ARE DIFFERENT AND
 MAY OR MAY NOT PROVIDE THE NEEDED COVERAGE. PLEASE SEE
 OTHER COMMENT WITH RESPECT TO STAIRS ON MOTION
 DETECTORS.
 PLEASE SEE SEPARATE SPACES WHICH REQUIRE DEVICES YET
 PLANS DO NOT INDICATE ANY DEVICES FOR THESE AREAS.
 PLEASE SEE THERE ARE MAXIMUM TIMES STATED IN THE FBC
 DEPENDING ON THE TYPES OF DEVICES CHOSEN. (OS TYPES
 30MINS)(TIMER TYPES 4HRS) THIS ALL DEPENDS ON DESIGN OF
 DEVICES ETC.
 PLEASE SEE THE SAME ENERGY CALCULATIONS WERE SUBMITTED
 BACK. PLEASE SEE THE RESPONSE MENTIONS HAVE BEEN
 PROPERLY SUBMITTED, HOWEVER PLEASE SEE NO INFORMATION
 PER 13-415.2 COULD BE FOUND ON PLANS AND OTHER
 DOCUMENTS SUBMITTED. PLEASE SEE THE FIXTURES AS SHOWN
 ON PLANS DO NOT ALL CORRELATE WITH THE FIXTURE LEGEND
 AND NO PERFORMANCE CALCULATIONS WERE LOCATED BASED ON
 THE FIXTURES ON PLANS AND SQ FT OF PROJECT ON HOW THE
 NUMBER OF 1.0 W/SF IS MET.
 THE DESIGN TOTAL COMPARED TO THE DESIGN ALLOWANCE BASED
 ON THE SECTION 13-415.2.C.1, 13-415.2.C.
 13-415.2.ABC.1.3
 PLEASE SEE AS THE SAME ENERGY CALCULATIONS FOR METHOD C
 WAS SUBMITTED BACK; PLEASE SEE THESE ARE STILL NOT
 SEALED AS REQUIRED AND PREVIOUSLY REQUESTED. PLEASE SEE
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND
 13-415.1.ABC.1.3 (WHERE APPLICABLE ON .1.3).PLEASE SEE
 13-103.1.1.1 WHICH REQUIRES THESE TO BE *SIGNED, DATED
 AND SEALED* BY THE DESIGN PROFESSIONAL OF RECORD AND
 RESPONSIBLE FOR THE DOCUMENTS.
 3) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED
 PHOTO-METRICS AND ANY CONTROLS TO MEET BOTH THE FBC AND
 NFPA-101 FOR DEVICES CHOSEN.
 PLEASE SEE THE PLANS NOW INDICATE ONLY ONE DEVICE ON
 EACH LEVEL FOR CONTROL OF EGRESS LIGHTING. PLEASE SEE
 7.9.2.2 OF THE LIFE SAFETY CODE WHICH WAS GIVEN ON BOTH
 OF THE PREVIOUS REVIEWS.
 FBC 1006.1.2, LS101 7.8.1.2.2
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE FIRST REVIEW COMMENTS WHICH GAVE
 NOTES FOR REQUIRED DEDICATED CIRCUITS FOR ELEVATOR
 ROOMS, EQUIPMENT ETC. THE RESPONSE WAS THE EQUIPMENT
 ROOM WAS TO HAVE DEDICATED CIRCUITS ETC AND THIS WAS
 DONE. PLEASE SEE 620.24 HOWEVER AS THIS REQUIRES
 DEDICATE BRANCH CIRCUIT FOR PIT LIGHTS AND RECEPTACLES.
 PLEASE SEE THE LIGHTING IS STILL SHOWN ON THE SAME
 CIRCUIT AS THE LIGHTING ON FIRST FLOOR.
  
 5) NOTE: PLEASE SEE THAT SOME LOAD CALCULATIONS FOR
 SERVICE ARE NOW BEING SUBMITTED FOR THE FIRST TIME FOR
 REVIEW. PLEASE SEE NO LOAD SUMMARY ON HOW LOADS WERE
 DERIVED WAS SUBMITTED.
 PLEASE SEE CONTINUOUS LOADS AS REQUIRED ARE STILL NOT
 SHOWN AT 125%.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON FUTURE LOADS
 AND CURRENT KNOWN
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE CLARIFY WHERE THE *85%* AS SHOWN AS A DE-RATING
 FOR * EQUIPMENT* COMES FROM BASED ON THE NEC. PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE AND EACH
 OF THE PANELS AS BEING SHOWN EVEN THOSE BEING SET ASIDE
 FOR FUTURE USE. PLEASE SEE THE ONLY PANEL SHOWN WHICH
 IS THE NHP AND THIS DOES NOT INCLUDE A LOAD SUMMARY OR
 HOW THE SERVICE WAS SIZED OR CORRECT LOAD CALCULATIONS
 FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
  
 6) NOTE: PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT
 COMPLETE.
 PLEASE SEE NO INFORMATION FOR ANY OF THE PROPOSED MAINS
 IS SHOWN. ONLY ONE OF THE MAINS INDICATES IT WILL BE
 800AMPS.
 PLEASE SEE NO AIC RATINGS FOR EACH OF THE SERVICE
 EQUIPMENT AND MAIN WAS SUBMITTED. SOME AIC CALCULATIONS
 THESE WAS SUBMITTED. 110.9
 PLEASE SEE NO MAINS AS REQUIRED PER 230.70, 230.71,
 230.72, 230.76 AND 230.79 ETC WAS SHOWN.
 IN FACT PLEASE SEE THE RESPONSE LETTER NOW MENTIONS
 SPECIFICALLY THAT A NEW SHUNT TRIP AND SHUNT TRIP
 BREAKERS WAS ADDED. THE RISER NOW SHOWS THIS AND AS
 PREVIOUSLY STATED IN BOTH PREVIOUS REVIEWS MAIN MUST
 MEET 230.76 AND 230.79. SHUNT TRIP BREAKERS AND SHUNT
 TRIPS DO NOT MEET CODE. PLEASE KNOW THAT ALL MAINS AND
 MEANS OF DISCONNECT MUST CONTAIN A MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED.
 PLEASE SEE THE LOCATION OF THESE MAINS SHALL BE LOCATED
 AT THE NEAREST POINT OF ENTRANCE INTO THE BUILDING.
 THIS IS A LIFE SAFETY HAZARD AND PROPERTY HAZARD. IF
 THERE IS A STRUCTURE FIRE FOR EXAMPLE AND THE ONLY WAY
 TO SHUT OFF THE POWER TO THE BUILDING IS LOCATED CLOSE
 TO THE CENTER OF THE BUILDING THIS WOULD NOT ONLY CAUSE
 A DELAY IT WOULD ALSO CREATE A HAZARD TO FIRE
 DEPARTMENT PERSONNEL IN AN EFFORT TO TURN OFF POWER.
 PLEASE SEE THERE ARE NUMEROUS ITEMS NOT COMPLETED ON
 RISER AT THIS TIME.
  
 ** AS A NOTE PANEL NHP IS GOING TO BE 800AMPS?
  
 7) NOTE: PLEASE SEE THE RISER STILL DOES NOT INDICATE
 THE GROUNDING ELECTRODE SYSTEM AS REQUIRED PER 250.50.
 PLEASE SEE THE RISER MENTIONS AND SHOWS ALL AS EXISTING
 HOWEVER THIS IS NOT POSSIBLE AS THE RISER JUST ABOVE
 WHICH SHOWS EXISTING CONDITIONS AND THIS DOES NOT
 CORRELATE WITH THE NEW PROPOSED RISER.
 HOW CAN THE GROUNDING ELECTRODE SYSTEM AS SHOWN BE
 EXISTING WHEN THE RISER AS SHOWN IS NEW?
 PLEASE ALSO SEE THAT 250.50 WHICH REQUIRES ALL FOOTER
 STEEL ETC TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE THE ADDITION AND NEW FOOTER STEEL OR
 BUILDING STEEL ETC IS REQUIRED TO BE PART OF THE
 SYSTEM.
 PLEASE SHOW NEW SYSTEM.
 250.50,250.54, 250.56 ETC.
 PLEASE ALSO SEE AS PREVIOUSLY NOTED IN REVIEWS: THE
 RISER IS STILL SHOWING *EQUIPMENT GROUNDING CONDUCTORS*
 AHEAD OF THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT
 PERMITTED. THIS CONDITION AS SHOWN WOULD CREATE
 OBJECTIONABLE CURRENTS AS STATED IN 250.6.
 PLEASE SEE 250.24 AS THIS REQUIRES BONDING AT THE FIRST
 MEANS OF DISCONNECT. WHEN THE BONDING IS DONE AT THE
 FIRST MEANS OF DISCONNECT AS REQUIRED PER 250.24 AND IF
 AN *EQUIPMENT GROUNDING CONDUCTOR IS INSTALLED BEFORE
 THE FIRST MEANS OF DISCONNECT THEN THIS WOULD BE
 PARALLELING THE NEUTRAL. (OBJECTIONABLE CURRENTS)
 PLEASE ADJUST RISER.
  
 8) NOTE: PLEASE SEE ONLY ONE SET OF PLANS CONTAIN
 SHEETS FOR A LIGHTNING PROTECTION SYSTEM.
 PLEASE SUBMIT TWO COMPLETED SET OF PLANS ALONG WITH NEW
 SHEETS FOR REVISED COMMENTS AS WELL AS LIGHTNING
 PROTECTION SHEETS.
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEWS STATED A NOTE
 WHICH SAID *PLEASE BE SURE TO CALL IF THERE ARE ANY
 QUESTIONS OR COMMENTS WITH RESPECT TO THE TYPED
 COMMENTS*. IT ALSO STATED * IF THERE ARE ANY COMMENT
 WHICH ARE NOT CLEAR IN ANY WAY, NOT UNDERSTOOD OR NOT
 TYPED IN A CLEAR MANOR, PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER*.
 PLEASE KNOW TO DATE NO CONTACT FROM THE DESIGNER OF
 RECORD HAS BEEN MADE.
 **PLEASE SEE PREVIOUS NOTES GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE SEVERAL OF THE CODE SECTIONS GIVEN ON ALL
 PREVIOUS REVIEWS STILL REMAIN. PLEASE SEE AS REQUIRED
 PER THE FLORIDA STATUTES 553.80(2)(B), A FEE HAS NOW
 BEEN ASSESSED AS REQUIRED FOR SAID REPEAT COMMENTS.
 THIS STATUTE APPLIES TO ANY OF THE SAME CODE COMPLIANT
 COMMENTS REPEATED.
 PLEASE SEE THE AMOUNT DUE BEFORE PLANS MAY BE
 RESUBMITTED IS 4X TIMES THE PORTION OF THE BASE PERMIT
 FEE ATTRIBUTED TO PLAN REVIEW. THE BASE PERMIT FEE WAS
 $12,500 AT 30% IS $3,750 TIME FOUR.THIS FEE IS
 $15,000.00.
 THIS FEE IS REQUIRED BEFORE PLANS MAY BE SUBMITTED. **
 IT IS STRONGLY RECOMMENDED THAT A MEETING BE HELD
 BETWEEN THE DESIGN TEAM AND THIS OFFICE ONCE ALL OF THE
 REVIEWS HAVE BEEN COMPLETED AS THE STATUTE REQUIRES THE
 FINE EACH TIME THEREAFTER AS WELL.
 PLEASE KNOW THAT PLANS ARE BEING RETAINED BY THIS
 OFFICE AND WILL BE PLACED WITH PLANS WHICH WERE
 RETAINED FROM PREVIOUS REVIEWS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 ALSO BEING RETAINED.
 PLEASE KNOW IF THERE IS A CONFLICT BETWEEN THE DESIGN
 TEAM OR DESIGNER WHICH IS NOT SETTLED ON A LOCAL LEVEL
 THE PLANS WILL BE FORWARD TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND STATES LEGAL COUNSEL TO THE
 BOARD FOR REVIEW.
 THIS INFORMATION WILL BE FORWARDED TO THE ASSISTANT
 BUILDING OFFICIAL MR. ROBERT BROWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-07 15:50:242007-07-07 15:50:24
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.