Plan Review Notes
Plan Review Notes For Permit 07010472
Permit Number 07010472
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-05-08 15:55:55*****UNSAT*****
  
  
 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 ACCESS TO THE FIRE HYDRANT, FIRE DEPARTMENT CONNECTION,
 OR ANY OTHER FIRE PROTECTION EQUIPMENT.COMMENT NOT
 FOUND ON SHEET LP-101 AS PER YOUR RESPONSE
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
 12.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE NEW
 FIRE DEPARTMENT CONNECTION (FDC).CONTACT WEST PALM
 BEACH FIRE PREVENTION (561-804-4724) FOR APPLICATIONS.
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722