2007-04-15 14:53:31 | ********* UNSAT2NDREVIEW *********** |
| |
| ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS |
| REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW |
| COMMENTS DUE TO CHANGES IN PLANS OR BASED ON PAPERWORK |
| AND DOCUMENTATION SUBMITTED NOT DONE BY ANY DESIGN |
| PROFESSIONAL |
| |
| ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| CORRECT. |
| PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| OCT 1ST OF 2005. PLEASE SEE THERE ARE SEVERAL CODES |
| WHICH ARE STILL BEING REFLECTED FROM THE *2001 FBC* , |
| THE 2000 FLORIDA ACCESSIBILITY CODE ETC? |
| PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE |
| CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC. |
| PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING |
| BUILDING ETC. |
| PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE |
| REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS |
| SHOWN AS THE 2002. |
| PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005 |
| NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1. |
| |
| ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL |
| REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED |
| FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF |
| THE OTHER TRADES. |
| |
| 2) NOTE: PLEASE SEE THE END OF THE PREVIOUS REVIEW |
| REQUESTED FOR ALL OLD/VOIDED SHEETS WHICH WERE BEING |
| REPLACED TO BE REMOVED AND TO SUBMIT *ONE COPY* OF THE |
| OLD/VOIDED SHEETS BACK WITH PLANS FOR REFERENCE. THE |
| SHEETS WERE REMOVED HOWEVER NO OLD/VOIDED SHEETS WERE |
| SUBMITTED BACK WITH PLANS? |
| PLEASE SUBMIT ALL FOR THE NEXT REVIEW AS SHEETS WILL BE |
| REQUIRED TO BE REMOVED AND REPLACED ON AGAIN. |
| |
| 3) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| THIS INFORMATION WHICH WAS SUBMITTED ON SEPARATE SHEETS |
| SHALL BE PART OF THE PLANS, SIGNED, DATED AND SEALED BY |
| THE RESPONSIBLE DESIGN PROFESSIONAL ALONG WITH TITLE |
| BLOCK INFORMATION ON PLANS AND SHEETS. THESE WOULD BE |
| INCORPORATED IN PLAN SETS NOT SUBMITTED AS LOOSE |
| SHEETS. |
| PLEASE ALSO THE INFORMATION ON SHEETS DOES NOT INDICATE |
| WHAT THESE ARE FOR? PLEASE SEE THAT ONLY A WORST CASE |
| IS BEING REQUESTED FOR BRANCH CIRCUITS AND FEEDERS. |
| PLEASE KNOW THIS WOULD INCLUDE SITE WIRING. THE |
| NUMERICAL DESIGNATIONS ON THESE SEPARATE SHEETS DO NOT |
| INDICATE WHAT THEY ARE FOR? |
| FBC 106.1.2, 106.3.5.1.2 |
| FS 471.025 |
| |
| 4) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND |
| PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE |
| AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2. |
| PLEASE SEE 13-101.1.6 FOR MINIMUM REQUIRED FOR SHELL AS |
| METHOD *B* AND *C*. PLEASE SEE THE SINGLE SHEET |
| SUBMITTED DOES NOT COORDINATE WITH ALL REQUIREMENTS |
| FROM THE 2004 FBC W/ 2006 REVISION AND FLA-COM UPDATED |
| FORM NUMBERS/METHODS. |
| PLEASE SEE THE ENERGY CALCULATIONS SHALL CORRELATE WITH |
| ALL FIXTURES AS SHOWN ON PLANS FOR DESIGN WATTAGE, TYPE |
| OF CONTROLS ETC. |
| PLEASE SEE 13-103.1.1.1 AS THE DESIGNER OF RECORD |
| RESPONSIBLE FOR PLANS/DESIGNS/ENERGY CALCULATIONS MUST |
| BE SIGNED, DATED AND SEALED AS STATED ON PREVIOUS |
| REVIEW. |
| * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, |
| BY THE ENGINEER OF RECORD. 13-103.1.1.1 |
| |
| 5) NOTE: PLEASE SEE THAT THE REQUIRED DEVICES FOR ALL |
| LIGHTING AND DETAIL FOR SYSTEM OR DEVICES WHICH ARE |
| GOING TO BE INSTALLED AND LOCATIONS ARE NOT SHOWN ON |
| PLANS FOR COMPLIANCE WITH CHAPTER 13 OF THE 2004 FBC W/ |
| 2006 REVISIONS. |
| PLEASE SEE THAT A SINGLE TC IS NOT THE ONLY ITEM |
| NEEDED. PLEASE SEE THAT OVER-RIDE DEVICES ARE REQUIRED |
| AT THE POINT OF ENTRANCE INTO SPACES AND THESE DEVICES |
| A LIMITED TO TIME OF OVER-RIDE DEPENDING ON THE DEVICE |
| WHICH IS SELECTED. PLEASE SEE ALL ROOMS AND SEPARATE |
| SPACES SHALL ALSO CONTAIN DEVICES WHICH ARE NOT SHOWN |
| AND MAXIMUM OVER RIDE TIMES. |
| PLEASE SEE THE SAME SECTIONS AS NOTED ON PREVIOUS |
| REVIEW. |
| PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED FOR |
| AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC |
| 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| PLEASE ALSO SEE THE STAIR AREAS WHICH ARE STATED AS |
| BEING LEFT IN THE *ON* POSITION WHICH DOES NOT MEET THE |
| INTEND OF THE FLORIDAENERGY CODE OR REQUIRED MANDATES |
| NATIONWIDE. |
| PLEASE SEE THERE ARE SECTIONS ON THE FBC AND NFPA WHICH |
| ADDRESS EGRESS PATHS AND STAIRS. PLEASE SEEFBC |
| 1006.1.2 |
| |
| 6) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE |
| REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED |
| AND REQUIRED PER NFPA-101 7.8.1.3, 7.9.2.2 |
| THE LOOSE SHEETS WHICH CONTAIN PHOTO-METRICS ARE DONE |
| PART OF THE PLANS; THEY DO NOT INDICATE THE STAIR |
| LIGHTING UNDER NORMAL OR EMERGENCY IN ANY FASHION WHICH |
| IS THE MOST IMPORTANT AREAS. THEY ARE NOT SIGNED, DATED |
| OR SEALED BY THE RESPONSIBLE DESIGNER OF RECORD AS |
| REQUIRED PER FS 471.025 |
| THEY DO NOT INDICATE THE OTHER EGRESS PATHS UNDER |
| NORMAL AND EMERGENCY CONDITIONS. |
| |
| PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR |
| SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO |
| EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE |
| SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE |
| FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM |
| NFPA-101. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11 |
| THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS |
| REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED |
| STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND |
| PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY |
| DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, |
| ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A |
| PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. |
| 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH |
| LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY |
| TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA |
| VALUES HEREIN SPECIFIED. |
| 7.8.1.2.2 AUTOMATIC, MOTION SENSOR, TYPE LIGHTING |
| SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, |
| PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR |
| FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET |
| FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR |
| IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA |
| SERVED BY THE LIGHTING UNITS. |
| 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN |
| AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND |
| EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE |
| ILLUMINATED AS FOLLOWS: |
| (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM |
| ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX |
| (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2) |
| THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING |
| SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF |
| AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE |
| FLOOR. |
| ***PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE |
| OF ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY |
| ONE EGRESS AREA IN TOTAL DARKNESS. PLEASE PLACE DEVICES |
| WHICH ARE TO CONTROL STAIRWAY LIGHTING FOR COVERAGE AND |
| THAT A MINIMUM OF TWO DEVICES CONTROL ANY ONE AREA. |
| |
| 7) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT ROOM. THE |
| LIGHT SWITCH IS LOCATED IN THE MIDDLE OF THE WALL WHERE |
| THE ELECTRICAL EQUIPMENT IS LOCATED. |
| PLEASE COORDINATE. |
| FBC 106.1.2 |
| |
| 8) NOTE: PLEASE CORRELATE RISER AND PLANS FOR THE MAIN |
| ELECTRICAL ROOM EQUIPMENT. PLEASE SEE THE PLANS |
| INDICATE A 400A METER AND MAIN AND THE RISER INDICATES |
| 800AMP? |
| PLEASE SEE THE LOCATION WILL REQUIRE FURTHER |
| CONSULTATION WITH THE FIRE MARSHAL'S OFFICE AS THE |
| LOCATION OF THE MAIN IS LOCATED INSIDE THE BUILDING |
| THROUGH A MINIMUM OF THREE LOCKED DOORS WHICH AT THIS |
| TIME IS TOO FAR INTO THE BUILDING FOR LIFE SAFETY AND |
| READY ACCESS TO MAIN IN THE EVENT OF AN EMERGENCY OR TO |
| SHUT OFF POWER DURING A FIRE. |
| PLEASE SEE NEC 230.70, 90.4 |
| FBC 104.6 |
| |
| 9) NOTE: PLEASE SEE THAT THE RISER IS ONLY NOW BEING |
| SUBMITTEDWITH MORE COMPLETEDINFORMATION FOR |
| CONDUCTORS, CONDUITS ETC, HOWEVER THERE ARE STILL SOME |
| ITEMS WHICH NEED TO BE INCLUDED FOR CODE COMPLIANCE AS |
| PREVIOUSLY NOTED. |
| PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE |
| AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| BE REVIEWED FOR CODE COMPLIANCE. |
| PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL |
| MISSING. |
| A) NO GROUNDING ELECTRODE SYSTEM. |
| B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT. |
| C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE |
| INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW |
| SHOWN ON RISER. (250.6, 250.24) |
| D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN |
| WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS |
| ETC SHOWN ARE OF ADEQUATE SIZE ETC. |
| SECTIONS AS GIVEN IN PREVIOUS REVIEW. |
| ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| 110.26 ETC. |
| PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| |
| 10) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE |
| IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED |
| FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS |
| NOTED ON PREVIOUS REVIEW. |
| ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| NOT ACCEPTABLE TO THIS AHJ. |
| 110.3, 90.4. |
| |
| 11) NOTE:PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR |
| PANEL NHP DOES NOT PROVIDE THE REQUIRED AND REQUESTED |
| INFORMATION FOR COMPLETE LOAD CALCULATIONS FOR SERVICE |
| AND ALL EQUIPMENT BY THE DESIGNER OF RECORD.ALL |
| INFORMATION SHALL BE INCLUDED IN RECORD SETS OF PLANS |
| AND NOT SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN |
| THE COMPLETED INFORMATION OR DONE BY THE DESIGNER OR |
| RECORD. |
| PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, |
| 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS |
| PREVIOUSLY NOTED. |
| PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE |
| AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING |
| SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL |
| SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD |
| SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD |
| CALCULATIONS FOR THIS PANEL OR SERVICE. |
| PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR |
| CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| NOT BE DETERMINED AT THIS TIME. |
| PLEASE SEE ALL OF 220. |
| PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| LOADS AND LARGEST MOTORS LOADS AT 125%. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 12) NOTE: PLEASE SEE THIS SAME COMMENT FROM PREVIOUS |
| REVIEW WHICH REMAINS AS NOT INFORMATION WAS SUBMITTED. |
| PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE AIC |
| RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE |
| CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2. |
| NEC 110.9 |
| |
| 13) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE |
| THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35. |
| PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS |
| IS ONLY SHOWN AS WHAT APPEARS TO BE A TWO SECTION PANEL |
| ON RISER AND RESPONSE MENTIONS THIS, HOWEVER PLANS, |
| RISER AND PANEL SCHEDULE DOES NOT SHOW IF THIS FIRST |
| SECTION CONTAINS FEED-THRU LUGS, FEEDERS, OCP ETC. |
| PLEASE PROVIDE INFORMATION. |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 14) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS |
| BEING ATTACHED WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| COMPLIANCE. |
| PLEASE SEE THIS IS GIVEN ONLY AS A NOTICE AT THIS |
| TIME. |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |