2007-04-15 14:53:31********* UNSAT2NDREVIEW ***********
  
 ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS
 REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO CHANGES IN PLANS OR BASED ON PAPERWORK
 AND DOCUMENTATION SUBMITTED NOT DONE BY ANY DESIGN
 PROFESSIONAL
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE SEE THERE ARE SEVERAL CODES
 WHICH ARE STILL BEING REFLECTED FROM THE *2001 FBC* ,
 THE 2000 FLORIDA ACCESSIBILITY CODE ETC?
 PLEASE ALSO SEE THAT AS OF DECEMBER 8TH, 2006 THE
 CODES CHANGED TO THE 2006 REVISIONS TO THE 2004 FBC.
 PLEASE SEE THIS INCLUDES ALL MECHANICAL, PLUMBING
 BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED ALONG WITH THE INCORRECT NFPA-70 WHICH IS
 SHOWN AS THE 2002.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVER SHEET AND ELECTRICAL PLANS AT A MINIMUM. 2005
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE. THIS IS FOR ELECTRICAL
 REVIEW ONLY HOWEVER ALL CORRECTED CODES MUST BE STATED
 FOR DESIGN WHETHER OR NOT COMMENTS ARE MADE BY ANY OF
 THE OTHER TRADES.
  
 2) NOTE: PLEASE SEE THE END OF THE PREVIOUS REVIEW
 REQUESTED FOR ALL OLD/VOIDED SHEETS WHICH WERE BEING
 REPLACED TO BE REMOVED AND TO SUBMIT *ONE COPY* OF THE
 OLD/VOIDED SHEETS BACK WITH PLANS FOR REFERENCE. THE
 SHEETS WERE REMOVED HOWEVER NO OLD/VOIDED SHEETS WERE
 SUBMITTED BACK WITH PLANS?
 PLEASE SUBMIT ALL FOR THE NEXT REVIEW AS SHEETS WILL BE
 REQUIRED TO BE REMOVED AND REPLACED ON AGAIN.
  
 3) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
 THIS INFORMATION WHICH WAS SUBMITTED ON SEPARATE SHEETS
 SHALL BE PART OF THE PLANS, SIGNED, DATED AND SEALED BY
 THE RESPONSIBLE DESIGN PROFESSIONAL ALONG WITH TITLE
 BLOCK INFORMATION ON PLANS AND SHEETS. THESE WOULD BE
 INCORPORATED IN PLAN SETS NOT SUBMITTED AS LOOSE
 SHEETS.
 PLEASE ALSO THE INFORMATION ON SHEETS DOES NOT INDICATE
 WHAT THESE ARE FOR? PLEASE SEE THAT ONLY A WORST CASE
 IS BEING REQUESTED FOR BRANCH CIRCUITS AND FEEDERS.
 PLEASE KNOW THIS WOULD INCLUDE SITE WIRING. THE
 NUMERICAL DESIGNATIONS ON THESE SEPARATE SHEETS DO NOT
 INDICATE WHAT THEY ARE FOR?
 FBC 106.1.2, 106.3.5.1.2
 FS 471.025
  
 4) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE
 AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2.
 PLEASE SEE 13-101.1.6 FOR MINIMUM REQUIRED FOR SHELL AS
 METHOD *B* AND *C*. PLEASE SEE THE SINGLE SHEET
 SUBMITTED DOES NOT COORDINATE WITH ALL REQUIREMENTS
 FROM THE 2004 FBC W/ 2006 REVISION AND FLA-COM UPDATED
 FORM NUMBERS/METHODS.
 PLEASE SEE THE ENERGY CALCULATIONS SHALL CORRELATE WITH
 ALL FIXTURES AS SHOWN ON PLANS FOR DESIGN WATTAGE, TYPE
 OF CONTROLS ETC.
 PLEASE SEE 13-103.1.1.1 AS THE DESIGNER OF RECORD
 RESPONSIBLE FOR PLANS/DESIGNS/ENERGY CALCULATIONS MUST
 BE SIGNED, DATED AND SEALED AS STATED ON PREVIOUS
 REVIEW.
 * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED,
 BY THE ENGINEER OF RECORD. 13-103.1.1.1
  
 5) NOTE: PLEASE SEE THAT THE REQUIRED DEVICES FOR ALL
 LIGHTING AND DETAIL FOR SYSTEM OR DEVICES WHICH ARE
 GOING TO BE INSTALLED AND LOCATIONS ARE NOT SHOWN ON
 PLANS FOR COMPLIANCE WITH CHAPTER 13 OF THE 2004 FBC W/
 2006 REVISIONS.
 PLEASE SEE THAT A SINGLE TC IS NOT THE ONLY ITEM
 NEEDED. PLEASE SEE THAT OVER-RIDE DEVICES ARE REQUIRED
 AT THE POINT OF ENTRANCE INTO SPACES AND THESE DEVICES
 A LIMITED TO TIME OF OVER-RIDE DEPENDING ON THE DEVICE
 WHICH IS SELECTED. PLEASE SEE ALL ROOMS AND SEPARATE
 SPACES SHALL ALSO CONTAIN DEVICES WHICH ARE NOT SHOWN
 AND MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THE SAME SECTIONS AS NOTED ON PREVIOUS
 REVIEW.
 PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED FOR
 AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO SEE THE STAIR AREAS WHICH ARE STATED AS
 BEING LEFT IN THE *ON* POSITION WHICH DOES NOT MEET THE
 INTEND OF THE FLORIDAENERGY CODE OR REQUIRED MANDATES
 NATIONWIDE.
 PLEASE SEE THERE ARE SECTIONS ON THE FBC AND NFPA WHICH
 ADDRESS EGRESS PATHS AND STAIRS. PLEASE SEEFBC
 1006.1.2
  
 6) NOTE: PLEASE SEE THAT THE PLANS ARE MISSING THE
 REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY REQUESTED
 AND REQUIRED PER NFPA-101 7.8.1.3, 7.9.2.2
 THE LOOSE SHEETS WHICH CONTAIN PHOTO-METRICS ARE DONE
 PART OF THE PLANS; THEY DO NOT INDICATE THE STAIR
 LIGHTING UNDER NORMAL OR EMERGENCY IN ANY FASHION WHICH
 IS THE MOST IMPORTANT AREAS. THEY ARE NOT SIGNED, DATED
 OR SEALED BY THE RESPONSIBLE DESIGNER OF RECORD AS
 REQUIRED PER FS 471.025
 THEY DO NOT INDICATE THE OTHER EGRESS PATHS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
  
 PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR
 SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO
 EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE
 SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE
 FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM
 NFPA-101.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR, TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2)
 THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING
 SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF
 AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE
 FLOOR.
 ***PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE
 OF ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY
 ONE EGRESS AREA IN TOTAL DARKNESS. PLEASE PLACE DEVICES
 WHICH ARE TO CONTROL STAIRWAY LIGHTING FOR COVERAGE AND
 THAT A MINIMUM OF TWO DEVICES CONTROL ANY ONE AREA.
  
 7) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT ROOM. THE
 LIGHT SWITCH IS LOCATED IN THE MIDDLE OF THE WALL WHERE
 THE ELECTRICAL EQUIPMENT IS LOCATED.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 8) NOTE: PLEASE CORRELATE RISER AND PLANS FOR THE MAIN
 ELECTRICAL ROOM EQUIPMENT. PLEASE SEE THE PLANS
 INDICATE A 400A METER AND MAIN AND THE RISER INDICATES
 800AMP?
 PLEASE SEE THE LOCATION WILL REQUIRE FURTHER
 CONSULTATION WITH THE FIRE MARSHAL'S OFFICE AS THE
 LOCATION OF THE MAIN IS LOCATED INSIDE THE BUILDING
 THROUGH A MINIMUM OF THREE LOCKED DOORS WHICH AT THIS
 TIME IS TOO FAR INTO THE BUILDING FOR LIFE SAFETY AND
 READY ACCESS TO MAIN IN THE EVENT OF AN EMERGENCY OR TO
 SHUT OFF POWER DURING A FIRE.
 PLEASE SEE NEC 230.70, 90.4
 FBC 104.6
  
 9) NOTE: PLEASE SEE THAT THE RISER IS ONLY NOW BEING
 SUBMITTEDWITH MORE COMPLETEDINFORMATION FOR
 CONDUCTORS, CONDUITS ETC, HOWEVER THERE ARE STILL SOME
 ITEMS WHICH NEED TO BE INCLUDED FOR CODE COMPLIANCE AS
 PREVIOUSLY NOTED.
 PLEASE SEE THE RISER AS SUBMITTED IS STILL NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE SOME OF THE ITEMS WHICH ARE STILL
 MISSING.
 A) NO GROUNDING ELECTRODE SYSTEM.
 B) NO AIC RATINGS FOR ALL SERVICE EQUIPMENT.
 C) AN EQUIPMENT GROUNDING CONDUCTOR MAY NOT BE
 INSTALLED BEFORE THE FIRST MEANS OF DISCONNECT AS NOW
 SHOWN ON RISER. (250.6, 250.24)
 D) LOADS CAN NOT BE VERIFIED FOR SERVICE RISER AS SHOWN
 WHICH WILL BE NOTED BELOW TO VERIFY IF THE CONDUCTORS
 ETC SHOWN ARE OF ADEQUATE SIZE ETC.
 SECTIONS AS GIVEN IN PREVIOUS REVIEW.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 10) NOTE: PLEASE SEE PLANS MENTION A LOCK OFF/ON DEVICE
 IS TO BE INSTALLED HOWEVER NO NOTES COULD BE LOCATED
 FOR TYPE OF DEVICE WHICH IS REQUIRED TO BE INSTALLED AS
 NOTED ON PREVIOUS REVIEW.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 11) NOTE:PLEASE SEE THE SEPARATE SHEETS SUBMITTED FOR
 PANEL NHP DOES NOT PROVIDE THE REQUIRED AND REQUESTED
 INFORMATION FOR COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND ALL EQUIPMENT BY THE DESIGNER OF RECORD.ALL
 INFORMATION SHALL BE INCLUDED IN RECORD SETS OF PLANS
 AND NOT SUBMITTED ON LOOSE SHEETS WHICH DO NOT CONTAIN
 THE COMPLETED INFORMATION OR DONE BY THE DESIGNER OR
 RECORD.
 PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12,
 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS
 PREVIOUSLY NOTED.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE
 AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING
 SET ASIDE FOR FUTURE USE. PLEASE SEE THE ONLY PANEL
 SHOWN WHICH IS THE NHP AND THIS DOES NOT INCLUDE A LOAD
 SUMMARY OR HOW THE SERVICE WAS SIZED OR CORRECT LOAD
 CALCULATIONS FOR THIS PANEL OR SERVICE.
 PLEASE SEE NOTE #9 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 12) NOTE: PLEASE SEE THIS SAME COMMENT FROM PREVIOUS
 REVIEW WHICH REMAINS AS NOT INFORMATION WAS SUBMITTED.
 PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE AIC
 RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2.
 NEC 110.9
  
 13) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE
 THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35.
 PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS
 IS ONLY SHOWN AS WHAT APPEARS TO BE A TWO SECTION PANEL
 ON RISER AND RESPONSE MENTIONS THIS, HOWEVER PLANS,
 RISER AND PANEL SCHEDULE DOES NOT SHOW IF THIS FIRST
 SECTION CONTAINS FEED-THRU LUGS, FEEDERS, OCP ETC.
 PLEASE PROVIDE INFORMATION.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 14) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS
 BEING ATTACHED WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 PLEASE SEE THIS IS GIVEN ONLY AS A NOTICE AT THIS
 TIME.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  