2007-06-14 12:47:55BUILDING PLAN REVIEW
 PERMIT: 07010472
 ADD: 5205 GREENWOOD AVE
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST SHEET SS-002 LOADS AND DESIGN CRITERIA
 NOTE (D) TO PROVIDE GEOTECHNICAL REPORTS.THE REPORTS
 SUBMITTED ARE COPIES NOT THE ORIGINAL SIGNED AND SEALED
 REPORTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE
 STAT: 61G15-23.002 ENGINEERS.
 FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 5-6A) COMPLIED.
  
 6B) 2ND REQUEST,DETAIL # 2 INDICATES A MONOLITHIC
 FOOTER GOING PAST THE STEEL FRAME WALL BY SEVERAL
 INCHES, HOW WILL THIS BE WATERPROOFED SO WATER WILL NOT
 OSMOSIS UNDER THE BOTTOM TRACK TO THE INTERIOR OF THE
 BUILDING? SHEET DETAIL 8 /AF-510 INDICATES THE USE OF A
 MEMBRANE FLASHING APPLIED TO THE 5/8" EXTERIOR
 DENSEGLASSGOLD SHEATHING.
 1403.8
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 WITH THIS TYPE OF CONSTRUCTION OR ALTRATION TO THE
 EXISTING BUILDING UNDER THE EXISTING CBS WITH STUCCO
 DIRECTLY APPLIED TO THE BLOCK, THE CODE WAS NOT
 CONCERNED WITH A 6" INSPECTION ZONE FOR TERMITES.WHEN
 APPLYING THE VENEER TO THE EXTERTIORTHIS CHANGES THE
 LEVEL OR GRADE ON THE EXTERIOR OF THE BUILDING. SHEET
 SB-502 DETAIL# 1 INDICATES THE FOOTING AND SLAB TOTAL
 12" IN THE VERTICAL DIMENSION. WITH THE 6" INSPECTION
 PANEL AND THE 12" MINIMUM REQUIREMENT FOR FOUNDATIONS
 THE MINIMUM VERTICAL HEIGHT OF THE FOUNDATION IS 18",
 PLEASE UPDATE THEA & S SHEETS.
  
 6C) 2ND REQUEST, BOTH DETAILS 1& 2 BOTH INDICATE THE
 USE OF STEEL NETWORKS VERTICLIP SLS & SLB , HOW ARE
 THEY FASTENED TO THE EXISTING STEEL DECK, SINCE THEY
 ARE PART OF CREATING THE EXTERIOR ENVELOPE (MAIN
 WINDFORCE-RESISTING SYSTEM) DO THEY HAVE ANY PRODUCT
 EVALUATION REPORTS?IF REPORTS ARE AVAILABLE HAVE
 THEY TAKEN A 1.33% IN WINDLOADS? PLEASE SEE ICC
 REPORT ERS 1903 FOR SL, SLB, SLS & SLT EXTERIOR CURTAIN
 WALL SYSTEM. PROVIDE PRODUCT APPROVALS.
  
 6D) 2ND REQUEST, THIS SAME DETAIL IT WOULD APPEAR THAT
 THERE IS A GAP BETWEEN THE EXISTING FLOOR SLAB AND THE
 NEWLY CREATED CURTAIN WALL SYSTEM, WHAT WILL BE USED TO
 STOP THE VOID IN THE WALL AT THE SLAB LEVEL, FIRE
 PROOFING MATERIALS? SHEET AF-302 INDICATE & PROVIDE
 DOCUMENTATION OFUL FIRE STOP SYSTEM? 717.2.3
 CONNECTIONS BETWEEN HORIZONTAL AND VERTICAL SPACES.
 FIREBLOCKING SHALL BE PROVIDED AT INTERCONNECTIONS
 BETWEEN CONCEALED VERTICAL STUD WALL OR PARTITION
 SPACES AND CONCEALED HORIZONTAL SPACES CREATED BY AN
 ASSEMBLY OF FLOOR JOISTS OR TRUSSES, AND BETWEEN
 CONCEALED VERTICAL AND HORIZONTAL SPACES SUCH AS OCCUR
 AT SOFFITS, DROP CEILINGS, COVE CEILINGS AND SIMILAR
 LOCATIONS.
 717.2.1 FIREBLOCKING MATERIALS.
 FIREBLOCKING SHALL CONSIST OF 2-INCH (51 MM) NOMINAL
 LUMBER OR TWO THICKNESSES OF 1-INCH (25 MM) NOMINAL
 LUMBER WITH BROKEN LAP JOINTS OR ONE THICKNESS OF
 0.719-INCH (18.3 MM) WOOD STRUCTURAL PANEL WITH JOINTS
 BACKED BY 0.719-INCH (18.3 MM) WOOD STRUCTURAL PANEL OR
 ONE THICKNESS OF 0.75-INCH (19 MM) PARTICLEBOARD WITH
 JOINTS BACKED BY 0.75-INCH (19 MM) PARTICLEBOARD.
 GYPSUM BOARD, CEMENT FIBER BOARD, BATTS OR BLANKETS OF
 MINERAL WOOL OR GLASS FIBER OR OTHER APPROVED MATERIALS
 INSTALLED IN SUCH A MANNER AS TO BE SECURELY RETAINED
 IN PLACE SHALL BE PERMITTED AS AN ACCEPTABLE FIREBLOCK.
 BATTS OR BLANKETS OF MINERAL OR GLASS FIBER OR OTHER
 APPROVED NONRIGID MATERIALS SHALL BE PERMITTED FOR
 COMPLIANCE WITH THE 10-FOOT (3048 MM) HORIZONTAL
 FIREBLOCKING IN WALLS CONSTRUCTED USING PARALLEL ROWS
 OF STUDS OR STAGGERED STUDS. LOOSE-FILL INSULATION
 MATERIAL SHALL NOT BE USED AS A FIREBLOCK UNLESS
 SPECIFICALLY TESTED IN THE FORM AND MANNER INTENDED FOR
 USE TO DEMONSTRATE ITS ABILITY TO REMAIN IN PLACE AND
 TO RETARD THE SPREAD OF FIRE AND HOT GASES. THE
 INTEGRITY OF FIREBLOCKS SHALL BE MAINTAINED.
 717.2.1.1 DOUBLE STUD WALLS. BATTS OR BLANKETS OF
 MINERAL OR GLASS FIBER OR OTHER APPROVED NONRIGID
 MATERIALS SHALL BE ALLOWED AS FIREBLOCKING IN WALLS
 CONSTRUCTED USING PARALLEL ROWS OF STUDS OR STAGGERED
 STUDS.
  
 6E) PROVISO: STEEL SHOP DRAWINGS TO BE REVIEWED BY
 DESIGN PROFESSIONALBEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
 6F) COMPLIED.
  
 7) SHEET AF-302
 7A)(1) THE QUESTION ASKED WAS WHAT TYPE OF MATERIAL WAS
 TO BE USED FOR THE EXTERIOR TRIM ON THE BUILDING.
 RESPONSE COMMENTS ARE THIS IS TO BE A DRYVIT INFINITY
 SYSTEM. SUBMITTED WASA
 FLORIDA COVERSHEET 2030- R1, WHEN YOU LOOK INTO THE
 REPORT THE BACK UP INFORMATION IS SUPPOSE TO BE A
 MIAMI-DADE REPORT NOA 01-0614.14 SUCH REPORT WAS NOT
 SUBMITTED.
 7A)(2) THERE ARE TWO ISSUE WITH THE USE OF EFIS WALL
 SYSTEMS AND THE USE OF EFIS TO BE USED AS TRIM.
 EFIS WALL SYSTEMS:2603.3
 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION,
 FOAM PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHERE TESTED IN THE MAXIMUM THICKNESS INTENDED FOR USE
 IN ACCORDANCE WITH ASTM E 84. LOOSE FILL-TYPE FOAM
 PLASTIC INSULATION SHALL
 BE TESTED AS BOARD STOCK FOR THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX.
 EFIS EXTERIOR TRIM:2603.5.4 FLAME
 SPREAD AND SMOKE-DEVELOPED INDEXES. FOAM PLASTIC
 INSULATION, EXTERIOR COATINGS AND FACINGS SHALL BE
 TESTED SEPARATELY IN THE THICKNESS
 INTENDED FOR USE, BUT NOT TO EXCEED 4 INCHES
 (102 MM), AND SHALL EACH HAVE A FLAME SPREAD INDEX OF
 25 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450 OR LESS
 AS DETERMINED IN
 ACCORDANCE WITH ASTM E 84.
 2603.5 EXTERIOR WALLS OF BUILDINGS
 OF ANY HEIGHT.
 EXTERIOR WALLS OF BUILDINGS OF TYPE I, II, III
 OR IV CONSTRUCTION OF ANY HEIGHT SHALL COMPLY WITH
 SECTIONS 2603.5.1 THROUGH 2603.5.7 . EXTERIOR WALLS OF
 COLD STORAGE BUILDINGS REQUIRED TO
 BE CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS,
 WHERE THE BUILDING IS MORE THAN ONE STORY IN HEIGHT,
 SHALL ALSO COMPLY WITH THE PROVISIONS OF SECTIONS
 2603.5.1 THROUGH 2603.5.7 .
 EXTERIOR WALLS OF BUILDINGS OF TYPE V
 CONSTRUCTION SHALL COMPLY WITH SECTIONS 2603.2 , 2603.3
 AND 2603.4 .
  
 7B) COMPLIED.
  
 8) COMPLIED.
  
 9A) PARTIALLY COMPLIED WE ARE STILL MISSING PRODUCT
 APPROVALS. ) 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BEOPENINGS AND
 THE BALANCE OF GLAZED OPENINGS IN THE REST OF THE
 BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.GLAZED
 OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. 2.
 GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE
 GRADE SHALL MEET THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 9B) PARTIALLY COMPLIED.PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICA TION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9C) PARTIALLY COMPLIED.) WPB ADMIN CODE 106.3*
 PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9D) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 1. WINDOWS
 A. FIXED -OK
 B) STOREFRONT - NOT SUBMITTED
 C) CIRCULAR FIXED FRAME- NOT SUBMITTED
 D) CURTAIN WALL
 2) GLAZED DOORS
 A) KANEER IR-350 NOT SUBMITTED
 B) HOLLOW METAL DOOR- OK
 3) TRANSOM NOT SUBMITTED
 4) SIDELIGHTS- NOT SUBMITTED
 5) MULLIONS
 6) LOUVERS- STATED NONE IN BUILDING?
 7) EFIS SYSTEMS WRONG BACK UP REPORT
 8) ROOF ASSEMBLIES
 A) MAIN ROOF FIRESTONE ULTRAPLY - NO ENHANCED
 FASTENING REQUIRES ENGINEERS SEAL AND SIGNATURE
 B) ROOF TILE OK
 C) STANDING SEAM- OK
 D) UNDERLAYMENTS- OK
 E) ROOF INSULATION- OK
 F) ROOF HATCH EXISTING
 G) PRE-MANUFACTURED A/C STANDS NEW COMMENT
  
 10) COMPLIED.
  
 11) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]