Plan Review Notes For Permit 07010472 |
Permit Number |
07010472 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-14 13:57:53 | -----------------DENIED-------------------- | | | | 1. PG MM-501, DETAIL 1: PLEASE PROVIDE FLORIDA PRODUCT | | APPROVAL SHEETS FOR MANUFACTURED CONDENSING UNIT | | STANDS. ALSO PLEASE SHOW COMPLIANCE WITH CLEARANCE | | REQUIREMENTS OF FBC TABLE 1509.7. | | | | 2. PLEASE PROVIDE A PLAN SHOWING FRESH AIR AND EXHAUST | | DUCT SIZES, ROUTING AND LOCATION OF 2ND FLOOR SLAB | | PENETRATIONS. IS THIS FLOOR RATED? ARE FIRE DAMPERS OR | | SHAFTS NEEDED AT THESE LOCATIONS? FBC 106.1.1 | | | | 3. PG MM-602 ELEVATOR MACHINE ROOM ACU SCHEDULE SHOWS 3 | | SEPERATE SPLIT SYSTEMS BUT ONLY ONE IS SHOWN ON PLANS. | | PLEASE CLARIFY PER FBC 106.1.1 | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|