2007-01-30 08:01:56 | *** UNSAT **** |
| |
| *** IMPORTANT*** |
| * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND |
| PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE |
| RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE |
| WHICH WERE NOT MADE ON THIS REVIEW. |
| |
| 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| CORRECT. |
| PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER |
| 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO |
| THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL, |
| PLUMBING BUILDING ETC. |
| PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE |
| REFLECTED. |
| PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM. |
| 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 |
| NFPA-1. |
| |
| ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL |
| REVIEW ONLY. |
| |
| 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS |
| SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS, |
| STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC |
| 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE |
| THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH |
| PLANS. |
| PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE |
| INDICATED. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 3) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION |
| SYSTEM SHALL BE REQUIRED TO BE UNDER A SEPARATE |
| PERMIT. |
| |
| 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION |
| FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE |
| INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE |
| PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT |
| THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON |
| PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS |
| IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE |
| MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A |
| *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON |
| PLANS. |
| ** PLEASE SEE FBC 2004. |
| FBC ADMIN SECTION 106.1.2 |
| |
| 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| |
| 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND |
| PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE |
| AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2. * |
| PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, BY |
| THE ENGINEER OF RECORD. 13-103.1.1.1 |
| |
| 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED |
| FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC |
| 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| |
| 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM |
| FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22, |
| 620.23, 620.24 AND 620.51. |
| PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM |
| AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT |
| FEED ANY OTHER AREAS. PLEASE SEE PLANS INDICATE THESE |
| CIRCUITS FEEDING OTHER LIGHTING OUTSIDE OF THESE |
| AREAS. |
| PLEASE ALSO SEE THE STATE ELEVATOR CODE. |
| PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR |
| MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11, |
| 620.12 ETC. |
| |
| 9) NOTE:PLEASE VERIFY THE LOCATION OF THE ROOF TOP |
| GFI REQUIRED FOR A/ C EQUIPMENT PER 210.63 AND |
| 210.8(B)(3). |
| |
| 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON |
| PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND. |
| PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS |
| TIME. |
| FBC 106.1.2. |
| |
| 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, |
| ELECTRICAL EQUIPMENT ROOM. |
| NFPA-101 7.8, 7.9 |
| NFPA-70 700.16, AND 700.12E. |
| |
| 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR |
| ALL EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3, |
| 7.9.2.2. |
| |
| 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE |
| AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| BE REVIEWED FOR CODE COMPLIANCE. |
| PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| 110.26 ETC. |
| PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| |
| 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY |
| 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2. |
| PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED |
| FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM |
| CONTROL PANEL. |
| ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| NOT ACCEPTABLE TO THIS AHJ. |
| 110.3, 90.4. |
| |
| 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN |
| THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THE |
| ONLY PANEL SHOWN WHICH IS THE NHP DOES NOT INCLUDE A |
| LOAD SUMMARY OR HOW THE SERVICE WAS SIZED. |
| PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR |
| CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| NOT BE DETERMINED AT THIS TIME. |
| PLEASE SEE ALL OF 220. |
| PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| LOADS AND LARGEST MOTORS LOADS AT 125%. |
| FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| |
| 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE |
| AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE |
| CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2. |
| NEC 110.9 |
| |
| 18) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE |
| THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35. |
| PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS |
| DOES NOT SHOW BEING A TWO SECTION OR CONTAINING |
| FEED-THRU LUGS ETC. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-01-29 12:49:58 | IN ELEC FOR REVIEW (ONE ROLL) AND PERMIT APPLICATION. |