Plan Review Notes
Plan Review Notes For Permit 07010472
Permit Number 07010472
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-30 08:01:56*** UNSAT ****
  
 *** IMPORTANT***
 * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND
 PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE
 RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE
 WHICH WERE NOT MADE ON THIS REVIEW.
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER
 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO
 THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL,
 PLUMBING BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE
 REFLECTED.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003
 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL
 REVIEW ONLY.
  
 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS
 SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS,
 STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC
 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE
 THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH
 PLANS.
 PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE
 INDICATED.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION
 SYSTEM SHALL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE
 INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE
 PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT
 THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON
 PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS
 IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE
 MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A
 *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON
 PLANS.
 ** PLEASE SEE FBC 2004.
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE
 AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2. *
 PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, BY
 THE ENGINEER OF RECORD. 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED
 FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM
 FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22,
 620.23, 620.24 AND 620.51.
 PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM
 AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT
 FEED ANY OTHER AREAS. PLEASE SEE PLANS INDICATE THESE
 CIRCUITS FEEDING OTHER LIGHTING OUTSIDE OF THESE
 AREAS.
 PLEASE ALSO SEE THE STATE ELEVATOR CODE.
 PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR
 MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11,
 620.12 ETC.
  
 9) NOTE:PLEASE VERIFY THE LOCATION OF THE ROOF TOP
 GFI REQUIRED FOR A/ C EQUIPMENT PER 210.63 AND
 210.8(B)(3).
  
 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND.
 PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS
 TIME.
 FBC 106.1.2.
  
 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP
 LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM,
 ELECTRICAL EQUIPMENT ROOM.
 NFPA-101 7.8, 7.9
 NFPA-70 700.16, AND 700.12E.
  
 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR
 ALL EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2.
  
 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY
 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2.
 PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED
 FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM
 CONTROL PANEL.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN
 THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THE
 ONLY PANEL SHOWN WHICH IS THE NHP DOES NOT INCLUDE A
 LOAD SUMMARY OR HOW THE SERVICE WAS SIZED.
 PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE
 AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2.
 NEC 110.9
  
 18) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE
 THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35.
 PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS
 DOES NOT SHOW BEING A TWO SECTION OR CONTAINING
 FEED-THRU LUGS ETC.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]