Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop G
Sequence Number 4
Notes
Date Text
2007-07-31 15:11:12NOTE: SENT TO LUIS MARTINEZ.
  
 ****************PROVISO****************
 PLEASE REFERENCE THE FOLLOWING FOR THE PLUMBING SERVICE
 SCHEDULE THAT REFLECTS THE EQUIPMENT SUBMITTAL. PLEASE
 REFERENCE THE RED LINE CORRECTIONS TO THE BTU LOAD ON
 THE NATURAL GAS RISER:
  
 G2 - RICE COOKER= 34,000 BTU'S:
 G5 - FRYER= 105,000 BTU'S:
 G6 - HOT PLATE= 44,000 BTU'S:
 G7 - BROILER= 120,000 BTU'S:
 G8 - GRIDDLE= 40,000 BTU'S:
 G9 - GYRO GRILL (SUBMITTAL BOOK IDENTIFIES ITEM AS A
 "VERTICAL BROILER")= 50,000 BTU'S:
  
 THE FOLLOWING IS THE CORRECT TOTAL OF KITCHEN EQUIPMENT
 BTU'S= 483,000 BTU'S:
  
 THE FOLLOWING IS THE CORRECT BTU TOTAL OF GAS SYSTEM
 INCLUDING WATER HEATER= 538,000 BTU'S:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  