Plan Review Notes
Plan Review Notes For Permit 07010448
Permit Number 07010448
Review Stop G
Sequence Number 3
Notes
Date Text
2007-07-06 17:09:33DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM THE PREVIOUS REVIEW:
 ********FROM PREVIOUS REVIEWS:
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, NOT ADDRESSED
 ********RESPONSE NOTED, BUT 4 OUT OF 6 GAS APPLIANCES
 HAVE ONLY A COVER SHEET FROM THE SUPPLIER AND NOT THE
 MANUF. SHEETS AS REQUESTED. THE MANUF. SHEETS ARE
 REQUIRED FOR ITEMS MARK G2, G6, G7 & G8 SHOWING A
 LISTING, INDICATE MODEL NUMBER, AND SHOW THE BTU LOAD
 THAT CORRELATES WITH THE PLUMBING SERVICE SCHEDULE AND
 THE GAS RISER DIAGRAM.
  
 C. N/A
 D. N/A
 E. OK
  
 ****NEW COMMENT:
  
 1B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]