2007-06-20 10:29:41 | *** UNSAT 3RDREVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF |
| FIXTURES, THE WATTAGE FOR FIXTURES, FIXTURE LEGEND AND |
| LIGHTING POWER DENSITIES. |
| PLEASE SEE THE WATTAGE ON FIXTURES |
| PLEASE SEE THE AMOUNT OF FIXTURES |
| PLEASE SEE THE TYPE OF FIXTURES |
| PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| |
| 2) NOTE: PLEASE SEE AS RISER HAS BEEN REVISED, PLEASE |
| SEE NO FLOATING NEUTRAL INDICATED ON RISER AT NEW |
| METER. 250.6 |
| |
| 3) NOTE: PLEASE INDICATE THE AIC RATING FOR THE NEW |
| MAIN. |
| |